[28]
Brake, no
warning
The brake is active and there are no
warnings.
[29]
Brake ready, no
fault
The brake is ready for operation and
there are no faults.
[30]
Brake fault
(IGBT)
The output is Logic ‘1’ when the brake
IGBT is short-circuited. Use this function
to protect the frequency converter if
there is a fault on the brake modules. Use
the output/relay to cut out the main
voltage from the frequency converter.
[33]
Safe Stop
Active
Indicates that the safe stop on terminal
37 is active.
[35]
External
Interlock
External Interlock function has been
activated via one of the digital inputs.
[40]
Out of ref
range
Active when the actual speed is outside
the settings in
4-52 Warning Speed Low
to
4-55 Warning Reference High
.
[41]
Below
reference low
Active when the actual speed is below
the speed reference setting.
[42]
Above
reference high
Active when the actual speed is above
the speed reference setting.
[45]
Bus Ctrl
Control output via bus. The state of the
output is set in
. The output state is retained in
the event of bus time-out.
[46]
Bus Ctrl 1 if
timeout
Controls output via bus. The state of the
output is set in
. In the event of bus time-out the
output state is set low (On).
[47]
Bus Ctrl 0 if
timeout
Controls output via bus. The state of the
output is set in
. In the event of bus time-out the
output state is set low (Off).
[55]
Pulse output
[60]
Comparator 0
See parameter group
13-1* Comparators
.
If Comparator 0 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[61]
Comparator 1
See parameter group
13-1* Comparators
.
If Comparator 2 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[62]
Comparator 2
See parameter group
13-1* Comparators
.
If Comparator 2 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[63]
Comparator 3
See parameter group
13-1* Comparators
.
If Comparator 3 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[64]
Comparator 4
See parameter group
13-1* Comparators
.
If Comparator 4 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[65]
Comparator 5
See parameter group
13-1* Comparators
.
If Comparator 4 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[70]
Logic Rule 0
See parameter group
13-4* Logic Rules
. If
Logic Rule 0 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[71]
Logic Rule 1
See parameter group
13-4* Logic Rules
If
Logic Rule 1 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[72]
Logic Rule 2
See parameter group
13-4* Logic Rules
. If
Logic Rule 2 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[73]
Logic Rule 3
See parameter group
13-4* Logic Rules
. If
Logic Rule 3 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[74]
Logic Rule 4
See parameter group
13-4* Logic Rules
. If
Logic Rule 4 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[75]
Logic Rule 5
See parameter group
13-4* Logic Rules
. If
Logic Rule 5 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
[80]
SL Digital
Output A
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[38] Set dig. out. A high
is executed.
The input will go low whenever the Smart
Logic Action
[32] Set dig. out. A low
is
executed.
[81]
SL Digital
Output B
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[39] Set dig. out. A high
is executed.
The input will go low whenever the Smart
Logic Action
[33] Set dig. out. A low
is
executed.
[82]
SL Digital
Output C
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[40] Set dig. out. A high
is executed.
The input will go low whenever the Smart
Logic Action
[34] Set dig. out. A low
is
executed.
[83]
SL Digital
Output D
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[41] Set dig. out. A
high is
executed. The input will go low whenever
the Smart Logic Action
[35] Set dig. out. A
low
is executed.
[84]
SL Digital
Output E
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[42] Set dig. out. A high
is executed.
The input will go low whenever the Smart
Logic Action
[36] Set dig. out. A low
is
executed.
Parameter Descriptions
Operating Instructions VLT
®
CDS302 and CDS303
64