Option Name
Description
[3]
Set-up 3
[4]
Set-up 4
[9]
Multi Set-up
Remote setup selections using digital inputs and the serial communication port. This setup used the
settings from
parameter -012 This Set-up Linked to
. Stop the drive before making changes to open-loop
and closed-loop functions.
Parameter 0-11 Edit Set-up
Table 14: Parameter 0-11 Edit Set-up
0-11 Edit Set-up
Default value: [1] Set-up 1
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the setup to be edited (that is programmed) during operation, either the active setup or 1 of the inactive setups.
Option Name
Description
[0]
Factory setup Cannot be edited, but it is useful as a data source to return the other setups to a known state.
[1]*
Set-up 1
[1] Set-up 1
to
[4] Set-up 4
can be edited freely during operation, independently of the active set-up.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Active Set-up Can also be edited during operation. Edit the selected setup from a range of sources: LCP, FC RS485, FC
USB, or up to 5 fieldbus sites.
AU373327181955en-000101 / 130R1208
34 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide