Option Name
Description
[3]
Option A
[30]
External can
[35]
Option A fast
Not applicable for current release.
[37]
Option C0 fast The reference is transferred faster and without jitter, which ensures more stability and dynamic con-
trol. Furthermore, all other references are ignored, which means that the drive is controlled by the C-
option reference only.
Parameter 8-03 Control Word Timeout Time
Table 411: 8-03 Control Word Timeout Time
8-03 Control Word Timeout Time
Default value: 1 s
Parameter type: Range, 0.1 - 18000 s
Setup: 1 setup
Conversion index: -1
Data type: Uint32
Change during operation: True
Enter the maximum time expected to pass between the reception of 2 consecutive telegrams. If this time is exceeded, it indicates
that the serial communication has stopped. The function selected in
parameter 8-04 Control Word Timeout Function
is then carried
out. A valid control word triggers the timeout counter.
Parameter 8-04 Control Word Timeout Function
Table 412: Parameter 8-04 Control Word Timeout Function
8-04 Control Word Timeout Function
Default value: Size related
Parameter type: Option
Setup: 1 setup
Conversion index: –
Data type: Uint8
Change during operation: True
Select the timeout function. The timeout function activates when the control word fails to be updated within the time period speci-
fied in
parameter 8-03 Control Word Timeout Time
.
N O T I C E
To change the setup after a timeout, configure as follows:
1. Set
parameter 0-10 Active Set-up
to
[9] Multi setup
.
2. Select the relevant link in
parameter 0-12 This Set-up Linked to
.
Option Name
Description
[0]
Off
Resumes control via fieldbus (fieldbus or standard), using the most recent control word.
[1]
Freeze output Freezes output frequency until communication resumes.
[2]
Stop
Stops with auto restart when communication resumes.
[3]
Jogging
Runs the motor at jog frequency until communication resumes.
[4]
Max. speed
Runs the motor at maximum frequency until communication resumes.
[5]
Stop and trip
Stops the motor, then resets the drive to restart:
Via the fieldbus.
Via [Reset].
Via a digital input.
AU373327181955en-000101 / 130R1208
204 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321