Option
Name
Description
[0]
FC profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
Parameter 8-13 Configurable Status Word STW
Table 418: Parameter 8-13 Configurable Status Word STW
8-13 Configurable Status Word STW
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the interpretation of the control and status words corresponding to the installed fieldbus. Only the selections valid for the
fieldbus installed in slot A are visible in the LCP display. For more guidelines in the selection of
[1] PROFIdrive profile
, refer to the
Installation Guide for the installed fieldbus.
Option Name
Description
[0]
No function
The input is always low.
[1]
Profile default
Dependent on the profile set in
parameter 8-10 Control Profile
.
[2]
Alarm 68 Only
The input goes high whenever
Alarm 68 Safe Stop Activated
is active and goes low when-
ever
Alarm 68 Safe Stop Activated
is not activated.
[3]
Trip excl Alarm 68
[10]
T18DI status
[11]
T19DI status
[12]
T27DI status
[13]
T29DI status
[14]
T32DI status
[15]
T33DI status
[16]
T37DI status
The input goes high whenever T37 has 0 V and goes low whenever T37 has 24 V.
[17]
X30/2 DI status
[18]
X30/3 DI status
[19]
X30/4 DI status
[20]
CTW timeout toggle inverse
[21]
Thermal warning
[30]
Brake fault (IGBT)
[40]
Out of ref range
[49]
Derate active
[54]
Running
AU373327181955en-000101 / 130R1208 | 207
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide