Option
Name
Description
[0]*
Current
[1]
Voltage
Parameter 16-62 Analog Input 53
Table 624: Parameter 16-62 Analog Input 53
16-62 Analog Input 53
Default Value: 0
Parameter Type: Range, -20 - 20
Setup: All set-ups
Conversion Index: -3
Data Type: Int32
Change during operation: False
View the actual value at input 53.
Parameter 16-63 Terminal 54 Switch Setting
Table 625: Parameter 16-63 Terminal 54 Switch Setting
16-63 Terminal 54 Switch Setting
Default Value: [0] Current
Parameter Type: Option
Setup: All set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: False
View the setting of terminal 54.
Option
Name
Description
[0]*
Current
[1]
Voltage
Parameter 16-64 Analog Input 54
Table 626: Parameter 16-64 Analog Input 54
16-64 Analog Input 54
Default Value: 0
Parameter Type: Range, -20 - 20
Setup: All set-ups
Conversion Index: -3
Data Type: Int32
Change during operation: False
View the actual value at input 54.
Parameter 16-65 Analog Output 42 [mA]
Table 627: Parameter 16-65 Analog Output 42 [mA]
16-65 Analog Output 42 [mA]
Default Value: 0
Parameter Type: Range, 0 - 30
Setup: All set-ups
Conversion Index: -3
Data Type: Int16
Change during operation: False
View the actual value at output 42 in mA. The value shown reflects the selection in
parameter 6-50 Terminal 42 Output
.
Parameter 16-66 Digital Output [bin]
Table 628: Parameter 16-66 Digital Output [bin]
16-66 Digital Output [bin]
Default Value: 0
Parameter Type: Range, 0 - 15
Setup: All set-ups
Conversion Index: 0
Data Type: Int16
Change during operation: False
AU373327181955en-000101 / 130R1208 | 311
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide