4.20.4 30-8* Compatibility (I)
Parameter 30-80 d-axis Inductance (Ld)
Table 717: Parameter 30-80 d-axis Inductance (Ld)
30-80 d-axis Inductance (Ld)
Default Value: Size related
Parameter Type: Range, 0.000 - 1000.000 mH
Setup: All set-ups
Conversion Index: -6
Data Type: Int32
Change during operation: False
Enter the value of the d-axis inductance. Obtain the value from the permanent magnet motor datasheet. The d-axis inductance
cannot be found by performing an AMA.
Parameter 30-81 Brake Resistor (ohm)
Table 718: Parameter 30-81 Brake Resistor (ohm)
30-81 Brake Resistor (ohm)
Default Value: Size related
Parameter Type: Range, 0.01 - 65535.00 ohm
Setup: 1 set-up
Conversion Index: -2
Data Type: Uint32
Change during operation: True
Set the brake resistor value in Ω. This value is used for monitoring the power to the brake resistor in
parameter 2-13 Brake Power
Monitoring
. This parameter is only active in drives with an integral dynamic brake.
Parameter 30-83 Speed PID Proportional Gain
Table 719: Parameter 30-83 Speed PID Proportional Gain
30-83 Speed PID Proportional Gain
Default Value: Size related
Parameter Type: Range, 0 - 1
Setup: All set-ups
Conversion Index: -4
Data Type: Uint32
Change during operation: True
Enter the speed controller proportional gain. Quick control is obtained at high amplification. However, if amplification is too great,
the process may become unstable.
Parameter 30-84 Process PID Proportional Gain
Table 720: Parameter 30-84 Process PID Proportional Gain
30-84 Process PID Proportional Gain
Default Value: Size related
Parameter Type: Range, 0 - 10
Setup: All set-ups
Conversion Index: -3
Data Type: Uint16
Change during operation: True
Enter the process controller proportional gain. Quick control is obtained at high amplification. However, if amplification is too great,
the process may become unstable.
Parameter 30-85 Motor Frequency
Table 721: Parameter 30-85 Motor Frequency
30-85 Motor Frequency
Default Value: Size related
Parameter Type: Range, 20.0 - 1000.0 Hz
Setup: All set-ups
Conversion Index: -1
Data Type: Uint32
Change during operation: False
N O T I C E
Changing this parameter affects the settings of other parameters.
Select the motor frequency from the motor nameplate data.
AU373327181955en-000101 / 130R1208