[P 5-13=Preset ref. bit 0]
Preset
[P 5-14=Preset ref. bit 1]
[P 5-15=Preset ref. bit 2]
10101010
76543210
29
12 (+24V)
11001100
32
11110000
33
e
3
0
b
a
1
4
9
.1
1
Illustration 42: Preset Reference
Table 179: Preset Referenece Bits
Preset ref. bit
2
1
0
Preset ref. 0
0
0
0
Preset ref. 1
0
0
1
Preset ref. 2
0
1
0
Preset ref. 3
0
1
1
Preset ref. 4
1
0
0
Preset ref. 5
1
0
1
Preset ref. 6
1
1
0
Preset ref. 7
1
1
1
Parameter 3-11 Jog Speed [Hz]
Table 180: Parameter 3-11 Jog Speed [Hz]
3-11 Jog Speed [Hz]
Default value: Size related
Parameter type: Range, 0 - par. 4-14 Hz
Setup: All setups
Conversion index: -1
Data type: Uint16
Change during operation: True
The jog speed is a fixed output speed at which the drive is running when the jog function is activated. See also
parameter 3-80 Jog/
Homing Ramp Time
.
Parameter 3-12 Catch Up/Slow Down Value
Table 181: Parameter 3-12 Catch Up/Slow Down Value
3-12 Catch Up/Slow Down Value
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
AU373327181955en-000101 / 130R1208
110 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide