Option Name
Description
[50]
On reference
[60]
Comparator 0
See
parameter group 13-1* Comparators
. If comparator 0 in SLC is true, the output goes high.
Otherwise, it is low.
[61]
Comparator 1
See
parameter group 13-1* Comparators
. If comparator 1 in SLC is true, the output goes high.
Otherwise, it is low.
[62]
Comparator 2
See
parameter group 13-1* Comparators
. If comparator 2 in SLC is true, the output goes high.
Otherwise, it is low.
[63]
Comparator 3
See
parameter group 13-1* Comparators
. If comparator 3 in SLC is true, the output goes high.
Otherwise, it is low.
[64]
Comparator 4
See
parameter group 13-1* Comparators
. If comparator 4 in SLC is true, the output goes high.
Otherwise, it is low.
[65]
Comparator 5
See
parameter group 13-1* Comparators
. If comparator 5 in SLC is true, the output goes high.
Otherwise, it is low.
[70]
Logic rule 0
See
parameter group 13-4* Logic Rules
. If logic rule 0 in SLC is true, the output goes high. Other-
wise, it is low.
[71]
Logic rule 1
See
parameter group 13-4* Logic Rules
. If logic rule 1 in SLC is true, the output goes high. Other-
wise, it is low.
[72]
Logic rule 2
See
parameter group 13-4* Logic Rules
. If logic rule 2 in SLC is true, the output goes high. Other-
wise, it is low.
[73]
Logic rule 3
See
parameter group 13-4* Logic Rules
. If logic rule 3 in SLC is true, the output goes high. Other-
wise, it is low.
[74]
Logic rule 4
See
parameter group 13-4* Logic Rules
. If logic rule 4 in SLC is true, the output goes high. Other-
wise, it is low.
[75]
Logic rule 5
See
parameter group 13-4* Logic Rules
. If logic rule 5 in SLC is true, the output goes high. Other-
wise, it is low.
[79]
PE power off
[80]
SL digital output A
See
parameter 13-52 SL Controller Action
. Output A is low on smart logic action
[32] Set digital
out A low
. Output A is high on smart logic action
[38]
.
[81]
SL digital output B
See
parameter 13-52 SL Controller Action
. Output B is low on smart logic action
[33] Set digital
out B low
. Output B is high on smart logic action
[39]
.
[82]
SL digital output C
See
parameter 13-52 SL Controller Action
. Output C is low on smart logic action
[34] Set digital
out C low
. Output C is high on smart logic action
[40]
.
[83]
SL digital output D
See
parameter 13-52 SL Controller 1 Action
. Output D is low on smart logic action
[35] Set digital
out D low
. Output D is high on smart logic action
[41]
.
[84]
SL digital output E
See
parameter 13-52 SL Controller Action
. Output E is low on smart logic action
[36] Set digital
out E low
. Output E is high on smart logic action
[42]
.
[85]
SL digital output F
See
parameter 13-52 SL Controller Action
. Output F is low on smart logic action
[37] Set digital
out F low
. Output F is high on smart logic action
[43]
.
[90]
kWh counter pulse
[120]
Local ref active
Output is high when
parameter 3-13 Reference Site
=
[2] Local
or when
parameter 3-13 Reference
Site
=
[0] Linked
to hand auto at the same time as the LCP is in hand-on mode.
AU373327181955en-000101 / 130R1208 | 167
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide