Enter the I
LOW
value. When the motor current drops below this limit, the display reads
Current Low
. The signal outputs can be pro-
grammed to produce a status signal on terminal 27 or 29 and on relay output 01 or 02. Refer to
Parameter 4-51 Warning Current High
Table 252: Parameter 4-51 Warning Current High
4-51 Warning Current High
Default value: Size related
Parameter type: Range, par. 4-50 - par. 16-37
Setup: All setups
Conversion index: -2
Data type: Uint32
Change during operation: True
Enter the I
HIGH
value. When the motor current exceeds this limit, the display reads
Current High
. The signal outputs can be program-
med to produce a status signal on terminal 27 or 29 and on relay output 01 or 02. Refer to
Parameter 4-52 Warning Speed Low
Table 253: Parameter 4-52 Warning Speed Low
4-52 Warning Speed Low
Default value: 0 RPM
Parameter type: Range, 0 - par. 16-37
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
Enter the n
LOW
value. When the motor speed exceeds this limit, the display reads
Speed low
. The signal outputs can be programmed
to produce a status signal on terminal 27 or 29 and on relay output 01 or 02.
Parameter 4-53 Warning Speed High
Table 254: Parameter 4-53 Warning Speed High
4-53 Warning Speed High
Default value: Size related
Parameter type: Range, par. 4-52 - 60000 RPM
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
Enter the n
HIGH
value. When the motor speed exceeds this value, the display reads
Speed high
. The signal outputs can be program-
med to produce a status signal on terminals 27 or 29 and on relay outputs 01 or 02. Refer to
Parameter 4-54 Warning Reference Low
Table 255: Parameter 4-54 Warning Reference Low
4-54 Warning Reference Low
Default value: -999999.999
Parameter type: Range, -999999.999 - par 4-55
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the lower reference limit. When the actual reference drops below this limit, the display indicates Ref
LOW
. The signal outputs
can be programmed to produce a status signal on terminal 27 or 29 and on relay output 01 or 02.
Parameter 4-55 Warning Reference High
Table 256: Parameter 4-55 Warning Reference High
4-55 Warning Reference High
Default value: 999999.999
Parameter type: Range, par 4-55 - 999999.999
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the upper reference limit. When the actual reference exceeds this limit, the display reads Ref
high
. The signal outputs can be
programmed to produce a status signal on terminal 27 or 29 and on relay output 01 or 02.
AU373327181955en-000101 / 130R1208
134 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide