Table 8: Quick Set-up Procedure
Press
Q2 Quick Menu.
Parameter 0-01 Language
Set language.
Parameter 1-20 Motor Power [kW]
Set motor nameplate power.
Parameter 1-22 Motor Voltage
Set nameplate voltage.
Parameter 1-23 Motor Frequency
Set nameplate frequency.
Parameter 1-24 Motor Current
Set nameplate current.
Parameter 1-25 Motor Nominal Speed
Set nameplate speed in RPM.
Parameter 5-12 Terminal 27 Digital In-
put
If terminal default is
[2] Coast in-
verse
, it is possible to change this
setting to
[0] No function
. No con-
nection to terminal 27 is then
needed for running AMA.
Parameter 1-29 Automatic Motor Adap-
tation (AMA)
Set desired AMA function. Enable
complete AMA is recommended.
AU373327181955en-000101 / 130R1208 | 27
Danfoss A/S © 2021.08
How to Program
VLT® AutomationDrive EZ FC 321
Programming Guide