Parameter 14-14 Kin. Back-up Time-up
Table 483: Parameter 14-14 Kin. Back-up Time-up
14-14 Kin. Back-up Time-up
Default value: 60 s
Parameter type: Range, 0 - 60 s
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: True
This parameter defines the kinetic back-up timeout in flux mode when running on low voltage grids. If the supply voltage does not
exceed the value defined in
parameter 14-11 Mains Fault Voltage Level
+5% within the specified time, the drive automatically runs a
controlled ramp-down profile before stop.
Parameter 14-15 Kin. Back-up Trip Recovery Level
Table 484: Parameter 14-15 Kin. Back-up Trip Recovery Level
14-15 Kin. Back-up Trip Recovery Level
Default value: Size related
Parameter type: Range, 0 - 60000.000 Reference- FeedbackUnit
Setup: All setups
Conversion index: -3
Data type: Uint32
Change during operation: True
This parameter specifies the kinetic back-up trip recovery level. The unit is defined in
parameter 0-02 Motor Speed Unit
.
Parameter 14-16 Kin. Back-up Gain
Table 485: Parameter 14-16 Kin. Back-up Gain
14-16 Kin. Back-up Gain
Default value: 100%
Parameter type: Range, 0 - 500%
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
Enter the kinetic back-up gain value in percent.
4.14.3 14-2* Trip Reset
Parameters for configuring auto reset handling, special trip handling, and control card self-test or initialization.
Parameter 14-20 Reset Mode
Table 486: Parameter 14-20 Reset Mode
14-20 Reset Mode
Default Value: [0] Manual reset
Parameter Type: Option
Setup: All set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: True
Select the reset function after tripping. Once reset, the drive can be restarted.
N O T I C E
The motor may start without warning. If the specified number of automatic resets is reached within 10 minutes, the drive enters
[0] Manual reset
mode. After the manual reset is performed, the setting of
parameter 14-20 Reset Mode
returns to the original se-
lection. If the number of automatic resets are not reached within 10 minutes, or when a manual reset is performed, the internal
automatic reset counter returns to 0.
Option
Name
Description
[0]*
Manual reset
Select
[0] Manual reset
to perform a reset via [Reset] or via the digital inputs.
[1]
Automatic reset x 1
Select
[1]
-
[12] Automatic reset
x 1… x20 to perform 1–20 automatic resets after tripping.
AU373327181955en-000101 / 130R1208
270 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide