14-22 Operation Mode
Option:
Function:
130BA097.12
FC 302
FC 301
FC 301 &
FC 302
13
12
18
37
32
27
19
29
33 20
50
39 42
54
53
55
19
18
12 13
20
33
27
32
Select
Initialization
[2] to reset all parameter
values to default settings, except for
,
, and
. The unit will reset during the
next power-up.
will also revert to the
default setting
Normal operation
[0].
[0]
*
Normal
operation
[1]
Control
card test
[2]
Initialisation
[3]
Boot mode
14-29 Service Code
Range:
Function:
0
*
[-2147483647 - 2147483647 ]
For internal service only.
14-50 RFI Filter
Option: Function:
[0]
Off Select
Off
[0] only if the unit is fed by an isolated
mains source (IT mains).
In this mode, the internal RFI filter capacitors between
chassis and the mains RFI filter circuit are cut-out to
reduce the ground capacity currents.
[1]
*
On Select
On
[1] to ensure that the unit complies with
EMC standards.
14-54 Bus Partner
Range:
Function:
1
*
[0 - 126 ]
6.7 15-0* Operating Data
Parameter group containing filter information such as
operating data, hardware configuration and software
versions.
6.7.1 15-0* Operating Data
15-00 Operating Hours
Range:
Function:
0 h
*
[0 - 2147483647 h] View how many hours the unit has
run. The value is saved when the unit
is turned off.
15-01 Running Hours
Range:
Function:
0 h
*
[0 - 2147483647
h]
View how many hours the filter has
run. Reset the counter in
15-07 Reset
Running Hours Counter
. The value is
saved when the unit is turned off.
15-03 Power Up's
Range:
Function:
0
*
[0 - 2147483647 ] View the number of times the unit has
been powered up.
15-04 Over Temp's
Range:
Function:
0
*
[0 - 65535 ] View the number of unit temperature faults
which have occurred.
15-05 Over Volt's
Range:
Function:
0
*
[0 - 65535 ] View the number of unit overvoltages which
have occurred.
15-07 Reset Running Hours Counter
Option:
Function:
[0]
*
Do not reset
[1]
Reset counter Select
Reset
[1] and press [OK] to reset the
Running Hours counter to zero (see
). This parameter cannot
be selected via the serial port, RS-485.
Select
Do not reset
[0] if no reset of the
Running Hours counter is desired.
6.7.2 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data
sources (
15-10 Logging Source
) at individual rates
). A trigger event (
15-12 Trigger
Event
) and window (
15-14 Samples Before Trigger
) are used
to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option:
Function:
Select which variables are to be
logged.
[0]
*
None
How to Programme
VLT Active Filter AAF 00x
MG.90.V2.02 - VLT® is a registered Danfoss trademark
67
6
6