0-10 Active Set-up
Option:
Function:
Select the set-up to control the filter
functions.
[0]
Factory setup Cannot be changed. It contains the Danfoss
data set, and can be used as a data source
when returning the other set-ups to a
known state.
[1]
*
Set-up 1
Set-up 1
[1] to
Set-up 4
[4] are the four
separate parameter set-ups within which all
parameters can be programmed.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Multi Set-up
Remote selection of set-ups using digital
inputs and the serial communication port.
This set-up uses the settings from
. Stop the filter before
making changes to open- and closed loop
functions
Use
to copy a set-up to one or all other
set-ups. Stop the filter before switching between set-ups
where parameters marked ‘not changeable during
operation’ have different values. To avoid conflicting
settings of the same parameter within two different set-
ups, link the set-ups together using
. Parameters which are ‘not changeable during operation’
are marked FALSE in the parameter lists in the section
Parameter Lists
.
0-11 Edit Set-up
Option:
Function:
Select the set-up to be edited (i.e.
programmed) during operation; either the
active set-up or one of the inactive set-ups.
[0]
Factory setup Cannot be edited but it is useful as a data
source to return the other set-ups to a
known state.
[1]
*
Set-up 1
Set-up 1
[1] to
Set-up 4
[4] can be edited
freely during operation, independently of
the active set-up.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Active Set-up Can also be edited during operation. Edit
the chosen set-up from a range of sources:
LCP, FC RS-485, FC USB or up to five fieldbus
sites.
0-12 This Set-up Linked to
Option:
Function:
To enable conflict-free changes from one set-up
to another during operation, link set-ups
0-12 This Set-up Linked to
Option:
Function:
containing parameters which are not
changeable during operation. The link will
ensure synchronising of the ‘not changeable
during operation’ parameter values when
moving from one set-up to another during
operation. ‘Not changeable during operation’
parameters can be identified by the label FALSE
in the parameter lists in the section
Parameter
Lists
.
is used by Multi set-
up in
. Multi set-up is used to
move from one set-up to another during
operation (i.e. while the filter is running).
Example:
Use Multi set-up to shift from Set-up 1 to Set-
up 2 whilst the motor is running. Programme in
Set-up 1 first, then ensure that Set-up 1 and
Set-up 2 are synchronised (or ‘linked’). Synchro-
nisation can be performed in two ways:
1. Change the edit set-up to
Set-up 2
[2] in
and set
to
Set-up 1
[1]. This will start the linking
(synchronising) process.
130BP075.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[1]
Setup 1
OR
2. While still in Set-up 1, copy Set-up 1 to Set-
up 2. Then set
to
Set-
up 2
[2]. This will start the linking process.
130BP076.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[2]
Setup 2
After the link is complete,
will read {1,2} to indicate that all ‘not
changeable during operation’ parameters are
now the same in Set-up 1 and Set-up 2. If there
are changes to a ‘not changeable during
operation’ parameter, e.g.
1-30 Stator Resistance
(Rs)
, in Set-up 2, they will also be changed
automatically in Set-up 1. A switch between
Set-up 1 and Set-up 2 during operation is now
possible.
[0]
*
Not linked
[1]
Set-up 1
How to Programme
VLT Active Filter AAF 00x
MG.90.V2.02 - VLT® is a registered Danfoss trademark
55
6