15-77 Slot C1 Option SW Version
Range:
Function:
0
*
[0 - 0 ] Software version for the installed option in option
slot C.
15-92 Defined Parameters
Array [1000]
Range:
Function:
0
*
[0 - 9999 ] View a list of all defined parameters in the
active filter. The list ends with 0.
15-93 Modified Parameters
Array [1000]
Range:
Function:
0
*
[0 - 9999 ] View a list of the parameters that have been
changed from their default setting. The list
ends with 0. Changes may not be visible until
up to 30 seconds after implementation.
15-98 Unit Identification
Range:
Function:
0 N/A
*
[0 - 0 N/A]
15-99 Parameter Metadata
Array [30]
Range:
Function:
0
*
[0 - 9999 ] This parameter contains data used by the MCT
10 Set-up Software.
6.8 16-0* General Status
16-00 Control Word
Range:
Function:
0
*
[0 - 65535 ] View the Control word sent from the unit via
the serial communication port in hex code.
16-03 Status Word
Range:
Function:
0
*
[0 - 65535 ] View the Status word sent from the unit via
the serial communication port in hex code.
16-30 DC Link Voltage
Range:
Function:
0 V
*
[0 - 10000 V] View a measured value. The value is filtered
with an 30ms time constant.
16-34 Heatsink Temp.
Range:
Function:
0 C
*
[0 - 255 C] View the heatsink temperature. The cut-out
limit is 90 ± 5
°
C, and the filter cuts back in at
60 ± 5
°
C.
16-35 Inverter Thermal
Range:
Function:
0 %
*
[0 - 100 %] View the percentage load on the inverter.
16-36 Inv. Nom. Current
Range:
Function:
Application
dependent
*
[0.01 - 10000.00 A] View the inverter
nominal current.
16-37 Inv. Max. Current
Range:
Function:
Application
dependent
*
[0.01 - 10000.00 A] View the inverter
maximum current.
16-39 Control Card Temp.
Range:
Function:
0 C
*
[0 - 100 C] View the temperature on the control card,
stated in
°
C
16-40 Logging Buffer Full
Option: Function:
View whether the logging buffer is full (see parameter
group 15-1*). The logging buffer will never be full
when
is set to
Log always
[0].
[0]
*
No
[1]
Yes
16-49 Current Fault Source
Range:
Function:
0
*
[0 - 8 ] Value indicates source of current faults including
short circuit, over current, and phase imbalance
(from left):
1-4 Inverter
5-8 Rectifier
0 No fault recorded
How to Programme
VLT Active Filter AAF 00x
MG.90.V2.02 - VLT® is a registered Danfoss trademark
71