6.8.1 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
*
[0 -
1023 ]
View the signal states from the active digital inputs.
Example: Input 18 corresponds to bit no. 5, ‘0’ = no
signal, ‘1’ = connected signal. Bit 6 works in the
opposite way, on = '0', off = '1' (safe stop input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/2
Bit 10-63
Reserved for future terminals
16-66 Digital Output [bin]
Range:
Function:
0
*
[0 - 15 ]
View the binary value of all digital outputs.
16-71 Relay Output [bin]
Range:
Function:
0
*
[0 - 511 ]
View the settings of all relays.
6.8.2 16-8* fieldbus & FC Port
Parameters for reporting the BUS references and control
words.
16-80 Fieldbus CTW 1
Range:
Function:
0
*
[0 - 65535 ] View the two-byte Control word (CTW)
received from the Bus-Master. Interpretation of
the Control word depends on the fieldbus
option installed and the Control word profile
selected in
8-10 Control Profile
.
For more information please refer to the
relevant fieldbus manual.
16-84 Comm. Option STW
Range:
Function:
0
*
[0 - 65535 ] View the extended fieldbus comm. option
status word.
For more information please refer to the
relevant fieldbus manual.
16-85 FC Port CTW 1
Range:
Function:
0
*
[0 - 65535 ] View the two-byte Control word (CTW)
received from the Bus-Master. Interpretation of
the control word depends on the fieldbus
option installed and the Control word profile
selected in
8-10 Control Profile
.
6.8.3 16-9* Diagnosis Read-Outs
16-90 Alarm Word
Range:
Function:
0
*
[0 - 4294967295 ] View the alarm word sent via the serial
communication port in hex code.
16-91 Alarm Word 2
Range:
Function:
0
*
[0 - 4294967295 ] View the alarm word sent via the serial
communication port in hex code.
16-92 Warning Word
Range:
Function:
0
*
[0 - 4294967295 ] View the warning word sent via the
serial communication port in hex code.
16-93 Warning Word 2
Range:
Function:
0
*
[0 - 4294967295 ] View the warning word sent via the serial
communication port in hex code.
How to Programme
VLT Active Filter AAF 00x
72