NOTE
A more complex Password protection is available for OEMs
upon request.
0-65 Quick Menu Password
Range:
Function:
200
*
[-9999 -
9999 ]
Define the password for access to the Quick
Menu via the [Quick Menu] key. If
0-66 Access to Quick Menu w/o Password
is
set to
Full access
[0], this parameter will be
ignored.
0-66 Access to Quick Menu w/o Password
Option:
Function:
[0]
*
Full access
Disables the password defined in
.
[1]
LCP: Read only Prevents unauthorised editing of Quick
Menu parameters.
[2]
LCP: No access Prevents unauthorised viewing and editing
of Quick Menu parameters.
[3]
Bus: Read only Read only functions for Quick Menu
parameters on fieldbus and/ or FC standard
bus.
[4]
Bus: No access No access to Quick Menu parameters is
allowed via fieldbus and/ or FC standard
bus.
[5]
All: Read only
read only function for Quick Menu
parameters on LCP, fieldbus or FC standard
bus.
[6]
All: No access
No access from LCP, fieldbus or FC
standard bus is allowed.
If
0-61 Access to Main Menu w/o Password
is set to
Full
access
[0] then this parameter will be ignored.
6.4 5-** Digital I/O Mode
6.4.1 5-0* Digital I/O Mode
Parameters for configuring the input and output using
NPN and PNP.
These parameters cannot be adjusted while motor is
running.
5-00 Digital I/O Mode
Option:
Function:
Digital inputs and programmed digital outputs are
pre-programmable for operation either in PNP or NPN
systems.
[0]
*
PNP Action on positive directional pulses
(↕)
. PNP systems
are pulled down to GND.
5-00 Digital I/O Mode
Option:
Function:
[1]
NPN Action on negative directional pulses
(↕)
. NPN
systems are pulled up to + 24 V, internally in the
filter.
NOTE
Once this parameter has been changed, it must be
activated by performing a power cycle.
This parameter cannot be adjusted while the motor is
running.
5-01 Terminal 27 Mode
Option:
Function:
[0]
*
Input
Defines terminal 27 as a digital input.
[1]
Output
Defines terminal 27 as a digital output.
5-02 Terminal 29 Mode
Option:
Function:
[0]
*
Input
Defines terminal 29 as a digital input.
[1]
Output
Defines terminal 29 as a digital output.
6.4.2 5-1* Digital Inputs
Parameters for configuring the input functions for the
input terminals.
The digital inputs are used for selecting various functions
in the filter. All digital inputs can be set to the following
functions:
Digital input function
Select
Terminal
No operation
[0]
All *term 32, 33
Reset
[1]
All
Stop inverse
[6]
All
Start
[8]
All *term 18
Latched start
[9]
All
Set-up select bit 0
[23]
All
Set-up select bit 1
[24]
All
Pulse input Time Based
[32]
29, 33
Follower AF # 1 Run
Feedback
[99]
All
Follower AF # 2 Run
Feedback
[100]
All
Sleep
[101]
T18, T19, T27, T29
Functions dedicated to only one digital input are stated in
the associated parameter.
5-10 Terminal 18 Digital Input
Option:
Function:
[0]
No operation
No reaction to signals transmitted to the
terminal.
How to Programme
VLT Active Filter AAF 00x
MG.90.V2.02 - VLT® is a registered Danfoss trademark
59
6