Control card, USB serial communication:
USB standard
1.1 (Full speed)
USB plug
USB type B “device” plug
Generic specifications:
Maximum parallel filters
4 on same CT set
Filter Efficiency
97%
Typical average switching frequency
3.0 – 4.5 kHz
Response time
< 0,5ms
Settling time - reactive current control
< 20ms
Settling time - harmonic current control
< 15ms
Overshoot – reactive current control
<10%
Overshoot – Harmonic current control
<10%
Connection to PC is carried out via a standard host/device
USB cable. The USB connection is galvanically isolated from
the supply voltage (PELV) and other high-voltage
terminals. The USB connection is not galvanically isolated
from protection earth. Use only isolated laptop/PC as
connection to the USB connector on the unit or an
isolated USB cable/converter.
Protection and Features:
•
Temperature monitoring of the heatsink ensures that the active filter trips if the temperature reaches a predefined
level. An overload temperature cannot be reset until the temperature of the heatsink is below the values stated in
the tables on the following pages.
•
If a mains phase is missing, the Active filter trips.
•
The active filter has a short circuit protection current rate of 100kA if properly fused
•
Monitoring of the intermediate circuit voltage ensures that the filter trips if the intermediate circuit voltage is too
low or too high.
•
The Active filter monitors the mains current as well as internal currents to reassure that current levels do not reach
critical levels. In case current exceed a critical level the filter trips.
AAF005A190T4E
21H2GCxx
AAF005A250T4E
21H2GCxx
AAF005A310T4
E21H2GCxx
AAF005A400T4E
21H2GCxx
Total
Current
[A]
190
250
310
400
Losses
Watt
[kW]
5
7
9
11
Needed Airflow
M
3
/h
765
1230
1230
1230
Frame
D
E
E
F
Nominal
Reactive
[A]
190
250
310
400
Nominal
Harmonic
[A]
170
225
280
360
Max individual harmonic
compensation in back channel
I
5
[A]
119
158
196
252
Nominal/
I
7
85
113
140
180
(maximum)
Note: Numbers are rounded to
nearest amp
I
11
54
72
90
115
I
13
48
63
78
101
I
17
34
45
56
72
I
19
31
41
50
65
I
23
27
36
45
58
I
25
24
32
39
50
General Specifications
VLT Active Filter AAF 00x
MG.90.V2.02 - VLT® is a registered Danfoss trademark
91