5-30 Terminal 27 Digital Output
Option:
Function:
[5]
Running
Motor is running and shaft torque
present.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
warning
An alarm or a warning activates the
output.
[12]
Current limit
The motor current is outside the range
set in
4-18 Current Limit
.
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the unit, the brake resistor, or the
thermistor.
[22]
Ready,no
thermal W
unit is ready for operation and there is no
over-temperature warning.
[24]
Ready, voltage
OK
unit is ready for operation and the mains
voltage is within the specified voltage
range (see
General Specifications
section in
the Designn Guide).
[26]
Bus OK
Active communication (no time-out) via
the serial communication port.
[55]
Pulse output
[122] No alarm
[125] Hand mode
Output is high when the unit is in Hand
on mode (as indicated by the LED light
above [Hand on]).
[126] Auto mode
[152] AF sleeping
5-31 Terminal 29 Digital Output
Option:
Function:
[0]
*
No operation Functions are described under 5-3*
Digital
Outputs
This parameter only applies to FC 302
6.4.4 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Option:
Function:
[0]
No operation
[128]
SC contactor
[129]
Mains contactor
5-41 On Delay, Relay
Array [9], (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Function:
0.01 s
*
[0.01 - 600.00 s] Enter the delay of the relay cut-in
time. Select one of available
mechanical relays and MCB 105 in an
array function. See
5-40 Function Relay
.
Relay 3-6 are included in MCB 113.
Selected
Event
Relay
output
Selected
Event
Relay
output
On Delay
P 5-41
On Delay
P 5-41
Off Delay
P 5-42
130BA171.10
5-42 Off Delay, Relay
Array [9] (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Function:
0.01 s
*
[0.01 - 600.00 s] Enter the delay of the relay cut-out
time. Select one of available
mechanical relays and MCB 105 in an
array function. See
5-40 Function Relay
.
Selected
Event
Relay
output
On Delay
P 5-41
Off Delay
P 5-42
130BA172.10
If the selected Event condition changes before the on- or
off delay timer expires, the relay output is unaffected.
How to Programme
VLT Active Filter AAF 00x
62