0-43 [Reset] Key on LCP
Option:
Function:
[0]
*
Disabled
No effect when [Reset] is pressed. Avoids
accidental alarm reset.
[1]
*
Enabled
[2]
Password
Avoids unauthorised resetting. If
is included in the
Quick Menu, then define the password in
.
[7]
Enabled
without OFF
Resets the frequency converter without
setting it in
Off
mode.
[8]
Password
without OFF
Resets the frequency converter without
setting it in
Off
mode. A password is
required when pressing [Reset] (see [2]).
6.3.7 0-5* Copy / Save
Copy parameter settings between set-ups and to/from the
LCP.
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
[1]
All to LCP
Copies all parameters in all set-ups
from the filter memory to the LCP
memory.
[2]
All from LCP
Copies all parameters in all set-ups
from the LCP memory to the filter
memory.
[3]
Size indep. from
LCP
Copy only the parameters that are
independent of the motor size. The
latter selection can be used to
programme several filters with the
same function without disturbing
motor data.
[4]
File from MCO to
LCP
[5]
File from LCP to
MCO
[6]
Data from DYN to
LCP
[7]
Data from LCP to
DYN
This parameter cannot be adjusted while the motor is
running.
0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function
[1]
Copy to set-
up 1
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up
) to Set-up 1.
0-51 Set-up Copy
Option:
Function:
[2]
Copy to set-
up 2
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up
) to Set-up 2.
[3]
Copy to set-
up 3
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up
) to Set-up 3.
[4]
Copy to set-
up 4
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up
) to Set-up 4.
[9]
Copy to all
Copies the parameters in the present set-up
over to each of the set-ups 1 to 4.
6.3.8 0-6* Password
0-60 Main Menu Password
Range:
Function:
100
*
[0 - 999 ] Define the password for access to the Main
Menu via the [Main Menu] key. If
0-61 Access
to Main Menu w/o Password
is set to
Full
access
[0], this parameter will be ignored.
0-61 Access to Main Menu w/o Password
Option:
Function:
[0]
*
Full access
Disables password defined in
.
[1]
LCP: Read only Prevent unauthorized editing of Main Menu
parameters.
[2]
LCP: No access Prevent unauthorized viewing and editing
of Main Menu parameters.
[3]
Bus: Read only Read-only functions for parameters on
fieldbus and/or FC standard bus.
[4]
Bus: No access No access to parameters is allowed via
fieldbus and/or FC standard bus.
[5]
All: Read only
Read-only function for parameters on LCP,
fieldbus or FC standard bus.
[6]
All: No access
No access from LCP, fieldbus or FC
standard bus is allowed.
If
Full access
[0] is selected then
0-65 Personal Menu Password
and
0-66 Access to Personal
Menu w/o Password
will be ignored.
How to Programme
VLT Active Filter AAF 00x
58