Manual 

 

 

EKC 315A Industrial Evaporator Controller 

 

© Danfoss USCO (HMR_MKS), 04-2008

 

 

USCO.PD.RD0.A1.22 /521U0092 

11

2.13 in

(54 mm)

1.77 in

(45 mm

)

2.84 in

(72 mm)

3.54 in

(90 mm)

Mounting:  DIN rail

Enclosure:  IP 20 (approximately NEMA 1)

Weight:  0.66 lbs (300 g)

Display:  LED, 3 digits

Terminals: Maximum 2.5 mm

2

 multicore

Technical Data

The supply voltage is galvanically isolated from the input and output 

signals, but the input and output signals are not galvanically isolated 

from each other. 

Supply voltage

24 V ac ± 15%, 50-60 Hz

80 VA maximum (5 VA for controller and additional 55 VA when the 

controllers powers the coil for an AKV/A pulse valve or an additional 

75 VA when used with the discontinued TQ valve).

Input signals

Current input signal on terminals 18 & 19, 4-20 mA or 0-20 mA

Pressure transmitter, 4-20 mA from AKS 33

Digital input on terminals 1 and 2 for start-stop of regulation

Temperature sensor input, 2 PT 1000

Analog output (terminals 2 and 5)

Current signal: 

4-20 mA or 0-20 mA

Load: 

  

200Ω maximum

2 Relay outputs

each SPST, AC-1/4A resistive or AC-15: 3A inductive

Ambient temperature

During operation:  +14°F to 131°F (-10 °C to 55°C)

During transport:   -40°F to 158°F (-40°C to 70°C)

Approvals

EU Low Voltage Directive complied and EMC demands re CE-marking 

complied with

LVD tested according to EN 60730-1 and EN 60730-2-9

EMC tested according to EN50081-1and EN 50082-2

Service Parameters for Troubleshooting (view only)

Description of parameter

Parameter

Units*

Current TQ valve’s (discontinued valve) actuator temperature

u04

°F or °C

Reference for TQ valve’s (discontinued valve) actuator temperature

u05

°F or °C

Analog input current signal (terminals 18 & 19) from PLC, etc. 

u06

mA

Analog output current signal on terminals 2 & 5

u08

mA

Digital input status. Combination of parameter r12 and terminals 1 & 2

u10

ON-OFF

Ongoing cut-in time for thermostat or duration of last completed cut-in

u18

minutes

Temperature of S2 temperature sensor (used for superheat)

u20

°F or °C

Current calculated superheat

u21

°F or °K

Controller’s superheat reference (target superheat controller is trying to achieve)

u22

°F or °K

Valve’s opening degree

u24

%

Evaporating pressure based on pressure transmitter

u25

psig or bar

Evaporating temperature based on pressure transmitter and selected refrigerant

u26

°F or °C

Temperature of S3 temperature sensor (used for thermostat function for solenoid valve)

u27

°F or °C

Control reference (se any offset provided by an input signal from a PLC or other 

source)

u28

°F or °C

Pressure transmitter current signal (terminals 14 & 15)

u29

mA

* The displayed units will depend on the units setting parameter r05.

Содержание EKC 315A

Страница 1: ...Manual REFRIGERATION AND AIR CONDITIONING Superheat controller EKC 315A...

Страница 2: ...ring 3 Operating principle 3 Operating the EKC 315A 4 5 Quick Setup Guide 6 Survey of functions settings and parameters 7 10 Service parameters for troubleshooting 11 Technical data 11 Wiring diagram...

Страница 3: ...ively small refrigerant charge the type ICM valve is recommended In systems with an AKV A valve the capacity can be distributed by using up to three valves in parallel When using more than one AKV A p...

Страница 4: ...r an error in regulation In this situation pushing the upper button for 1 second will cause the alarm or error code to be displayed When an alarm code is displayed by pushing the upper button the alar...

Страница 5: ...parameter you have scrolled to Press the both buttons simultaneously To increase the setting Press the upper button To decrease the setting Press the lower button To save the new setting and return to...

Страница 6: ...actuator s default settings input setting 2 Enter the pressure transmitters working range in parameters o20 min value and o21 max value Note These settings must be entered in gauge pressure and most t...

Страница 7: ...for example for loss due to a long sensor cable r09 18 F 10 K 18 F 10 K 0 F 0 K Offset of temperature sensor S3 signal To calibrate the sensor reading or to compensate for example for loss due to a lo...

Страница 8: ...half n19 0 2 1 0 0 3 Amplification factor for superheat only in 1 1 systems This setting determines the ICM or AKV valve s opening degree as a function of the change in evaporating pressure An increas...

Страница 9: ...fset At maximum AI the offset will be as set in parameter r06 o10 0 4 0 Frequency Must be set to the frequency of the 24 Vac power source o12 0 50 Hz 1 60 Hz 0 50 Hz Selection of normal display conten...

Страница 10: ...F 35 C Value of analog output at maximum current terminals 2 5 only applicable to AKV A or TQ Upper end of temperature or opening degree range that will yield a current output of 20 mA o28 94 F 70 C 3...

Страница 11: ...ctive complied and EMC demands re CE marking complied with LVD tested according to EN 60730 1 and EN 60730 2 9 EMC tested according to EN50081 1and EN 50082 2 Service Parameters for Troubleshooting vi...

Страница 12: ...tional power source needed Terminal pairs Description 17 18 Signal from TQ discontinued valve actuator See Appendix 1 for TQ wiring diagram 18 19 Optional current input from PLC or other source for of...

Страница 13: ...er than the integration time Tn parameter n05 time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1 2 times Tp 2 Wait until the system is in balance again 3 If there is still oscillation reduce Kp initi...

Страница 14: ...o types of superheat regulation load defined control and adaptive control are shown below For industrial refrigeration applications load defined control should be tried first Load defined superheat Th...

Страница 15: ...Manual EKC 315A Industrial Evaporator Controller 15 USCO PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008...

Страница 16: ...O PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008 Danfoss Inc Refrigeration Air Conditioning Division 7941 Corporate Drive Baltimore MD 21236 Ph 410 931 8250 Fax 410 931 8256 E mail baltimore danfo...

Отзывы: