background image

Manual 

EKC 315A  Industrial Evaporator Controller 

14 

 

USCO.PD.RD0.A1.22 / 521U0092

 

© Danfoss USCO (HMR_MKS), 04-2008

Appendix 1: Wiring diagram for discontinued TQ valve

Appendix 3

Wiring diagram for applications that use more than one AKV/A 
pulse width modulating expansion valve in parallel to control 
the refrigerant flow to a single evaporator.  This strategy is used 
in situations where the evaporator to be controlled exceeds the 
capacity of a single expansion valve.
Remember to set parameter o09 in both the EKC 315A and the 
EKC 347.

Appendix 4

If there are two evaporators sharing the same suction line, the 
signal from the pressure transmitter can be used by up to two 
controllers. 

Appendices

These appendices are referenced in various parts of the text. 

Appendix 2

The two types of superheat regulation, load-defined control and 
adaptive control are shown below. For industrial refrigeration 
applications, load-defined control should be tried first. 

Load-defined superheat

The reference follows a defined curve. This curve is defined by 
three values: the superheat value that will close the expansion 
valve (parameter n22), the minimum superheat reference value 
(parameter n10), and the maximum superheat reference value 
(parameter n09). These three values must be selected in such 
a way that the curve is situated between the minimum stable 
superheat (MSS) curve and the curve for average temperature 
difference 

Tm (temperature difference between media tem-

perature and evaporating temperature).

Adaptive superheat

Regulation is based on evaporator load by establishing mini-
mum stable superheat (MSS). The superheat reference is lowered 
to the exact point where instability begins. 
The superheat is limited by the settings for minimum and maxi-
mum superheat.

Содержание EKC 315A

Страница 1: ...Manual REFRIGERATION AND AIR CONDITIONING Superheat controller EKC 315A...

Страница 2: ...ring 3 Operating principle 3 Operating the EKC 315A 4 5 Quick Setup Guide 6 Survey of functions settings and parameters 7 10 Service parameters for troubleshooting 11 Technical data 11 Wiring diagram...

Страница 3: ...ively small refrigerant charge the type ICM valve is recommended In systems with an AKV A valve the capacity can be distributed by using up to three valves in parallel When using more than one AKV A p...

Страница 4: ...r an error in regulation In this situation pushing the upper button for 1 second will cause the alarm or error code to be displayed When an alarm code is displayed by pushing the upper button the alar...

Страница 5: ...parameter you have scrolled to Press the both buttons simultaneously To increase the setting Press the upper button To decrease the setting Press the lower button To save the new setting and return to...

Страница 6: ...actuator s default settings input setting 2 Enter the pressure transmitters working range in parameters o20 min value and o21 max value Note These settings must be entered in gauge pressure and most t...

Страница 7: ...for example for loss due to a long sensor cable r09 18 F 10 K 18 F 10 K 0 F 0 K Offset of temperature sensor S3 signal To calibrate the sensor reading or to compensate for example for loss due to a lo...

Страница 8: ...half n19 0 2 1 0 0 3 Amplification factor for superheat only in 1 1 systems This setting determines the ICM or AKV valve s opening degree as a function of the change in evaporating pressure An increas...

Страница 9: ...fset At maximum AI the offset will be as set in parameter r06 o10 0 4 0 Frequency Must be set to the frequency of the 24 Vac power source o12 0 50 Hz 1 60 Hz 0 50 Hz Selection of normal display conten...

Страница 10: ...F 35 C Value of analog output at maximum current terminals 2 5 only applicable to AKV A or TQ Upper end of temperature or opening degree range that will yield a current output of 20 mA o28 94 F 70 C 3...

Страница 11: ...ctive complied and EMC demands re CE marking complied with LVD tested according to EN 60730 1 and EN 60730 2 9 EMC tested according to EN50081 1and EN 50082 2 Service Parameters for Troubleshooting vi...

Страница 12: ...tional power source needed Terminal pairs Description 17 18 Signal from TQ discontinued valve actuator See Appendix 1 for TQ wiring diagram 18 19 Optional current input from PLC or other source for of...

Страница 13: ...er than the integration time Tn parameter n05 time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1 2 times Tp 2 Wait until the system is in balance again 3 If there is still oscillation reduce Kp initi...

Страница 14: ...o types of superheat regulation load defined control and adaptive control are shown below For industrial refrigeration applications load defined control should be tried first Load defined superheat Th...

Страница 15: ...Manual EKC 315A Industrial Evaporator Controller 15 USCO PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008...

Страница 16: ...O PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008 Danfoss Inc Refrigeration Air Conditioning Division 7941 Corporate Drive Baltimore MD 21236 Ph 410 931 8250 Fax 410 931 8256 E mail baltimore danfo...

Отзывы: