background image

Manual 

EKC 315A  Industrial Evaporator Controller 

 

USCO.PD.RD0.A1.22 / 521U0092

 

© Danfoss USCO (HMR_MKS), 04-2008

Operating the EKC 315A

The Display

The EKC 315A has a three character digital display. Four status LEDs 
(Light Emitting Diodes) are to the left of the numerals. To the right of 
the display are two push buttons.

By default, the display normally shows the superheat but user 
programming allows the valve’s opening degree or air temperature 
to be selected as the normal display.  At any given time, depressing 
the lower pushbutton will change from what was selected to be 
in the normal display to one of the other values depending on the 
setting in parameter o17, which will be displayed for 5 seconds.

The default setting is for °C and bar to be shown in the display, but 
the units can easily be changed to °F and psig.  See parameter r05.

The Front Panel LEDs

The upper LED (next to the valve symbol) lights to indicate the 
valve’s opening degree.  A short pulse indicates a small liquid flow 
and a long pulse a heavy liquid flow.

The LED next to the snowflake symbol lights to indicate that the 
controller is calling for refrigeration. 

The three lowermost LED’s will flash, if there is an alarm or an error in 
regulation.  In this situation, pushing the upper button for 1 second 
will cause the alarm or error code to be displayed.

When an alarm code is displayed by pushing the upper button, the 
alarm relay will be cut out.

The error (prefix E), alarm (prefix A), and status (prefix S) codes that 

can appear, along with the meaning of each code,  are given in the 

table below.  

Error, Alarm, and Status Codes

Code

Description

E1

Errors in the controller

E11

TQ valve’s actuator temperature outside its range (discontinued valve)

E15

Temperature sensor S2 (for superheat calculation) has a bad connection

E16

Temperature sensor S2 (for superheat calculation) is shortcircuited

E17

Temperature sensor S3 (air temperature sensor) has a bad connection

E18

Temperature sensor S3 (air temperature sensor) is shortcircuited

E19

The analog input signal on terminals 18 & 19 is outside the range

E20

The pressure transmitter signal on terminals 14 & 15 is outside the range

A1

High temperature alarm A1 has been detected (sensor S3)

A2

Low temperature alarm A2 has been detected (sensor S3)

A11

No refrigerant has been selected in parameter o30

S10

Regulation stopped by internal (par. r12) or external (terminals 1and 2) start/stop

S11

Thermostat relay is cut out

LED's on front panel

Opening signal to valve

Controller in refrigeration mode

Indicates an alarm, or a controller error

Indicates an alarm, or a controller error

T

Содержание EKC 315A

Страница 1: ...Manual REFRIGERATION AND AIR CONDITIONING Superheat controller EKC 315A...

Страница 2: ...ring 3 Operating principle 3 Operating the EKC 315A 4 5 Quick Setup Guide 6 Survey of functions settings and parameters 7 10 Service parameters for troubleshooting 11 Technical data 11 Wiring diagram...

Страница 3: ...ively small refrigerant charge the type ICM valve is recommended In systems with an AKV A valve the capacity can be distributed by using up to three valves in parallel When using more than one AKV A p...

Страница 4: ...r an error in regulation In this situation pushing the upper button for 1 second will cause the alarm or error code to be displayed When an alarm code is displayed by pushing the upper button the alar...

Страница 5: ...parameter you have scrolled to Press the both buttons simultaneously To increase the setting Press the upper button To decrease the setting Press the lower button To save the new setting and return to...

Страница 6: ...actuator s default settings input setting 2 Enter the pressure transmitters working range in parameters o20 min value and o21 max value Note These settings must be entered in gauge pressure and most t...

Страница 7: ...for example for loss due to a long sensor cable r09 18 F 10 K 18 F 10 K 0 F 0 K Offset of temperature sensor S3 signal To calibrate the sensor reading or to compensate for example for loss due to a lo...

Страница 8: ...half n19 0 2 1 0 0 3 Amplification factor for superheat only in 1 1 systems This setting determines the ICM or AKV valve s opening degree as a function of the change in evaporating pressure An increas...

Страница 9: ...fset At maximum AI the offset will be as set in parameter r06 o10 0 4 0 Frequency Must be set to the frequency of the 24 Vac power source o12 0 50 Hz 1 60 Hz 0 50 Hz Selection of normal display conten...

Страница 10: ...F 35 C Value of analog output at maximum current terminals 2 5 only applicable to AKV A or TQ Upper end of temperature or opening degree range that will yield a current output of 20 mA o28 94 F 70 C 3...

Страница 11: ...ctive complied and EMC demands re CE marking complied with LVD tested according to EN 60730 1 and EN 60730 2 9 EMC tested according to EN50081 1and EN 50082 2 Service Parameters for Troubleshooting vi...

Страница 12: ...tional power source needed Terminal pairs Description 17 18 Signal from TQ discontinued valve actuator See Appendix 1 for TQ wiring diagram 18 19 Optional current input from PLC or other source for of...

Страница 13: ...er than the integration time Tn parameter n05 time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1 2 times Tp 2 Wait until the system is in balance again 3 If there is still oscillation reduce Kp initi...

Страница 14: ...o types of superheat regulation load defined control and adaptive control are shown below For industrial refrigeration applications load defined control should be tried first Load defined superheat Th...

Страница 15: ...Manual EKC 315A Industrial Evaporator Controller 15 USCO PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008...

Страница 16: ...O PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008 Danfoss Inc Refrigeration Air Conditioning Division 7941 Corporate Drive Baltimore MD 21236 Ph 410 931 8250 Fax 410 931 8256 E mail baltimore danfo...

Отзывы: