Description of setting

Parameter Minimum Maximum Factory 

setting

Field 

setting

Setpoint for thermostat function for controlling a liquid line solenoid valve

Not used for superheat function. Used only for thermostat function.

Regulation is based on this user-set value unless there is a displacement of 

setpoint by an analog signal (see parameter 010). 

This setting is not changed by entering the parameter list, but by pushing both 

buttons simultaneously, then using the buttons individually to adjust the setpoint 

up and down (see the section “Operating the EKC 315A.”)

-

-76°F

(-60°C)

122°F

(50°C)

50°F

(10°C)

Differential for thermostat function

When temperature is higher than reference plus this user-set differential, 

the solenoid valve’s relay will be energized. It will be de-energized when the 

temperature drops below the setpoint. 

r01

0.2°F

(0.1°K)

36°F

(20°K)

3.6°F

(2.0°K)

Units

Setting 0:  °C and bar

Setting 1:  °F and psig

r05

C - b

(0)

F- P

(1)

C - b

(0)

Maximum displacement of thermostat setting or superheat reference

 

by an analog signal from a PLC or other external device. Determines how great 

a displacement will be added when the input signal is maximum (20 mA).  (See 

parameter o10.)

r06

-90°F

(- 50°K)

90°F

(50°K)

0°F

(0°K)

Offset of temperature sensor S2 signal

To calibrate the sensor reading, or to compensate, for example, for loss due to a 

long sensor cable. 

r09

-18°F

(-10°K)

18°F

(10°K)

0°F

(0°K)

Offset of temperature sensor S3 signal

To calibrate the sensor reading, or to compensate, for example, for loss due to a 

long sensor cable. 

r10

-18°F

(-10°K)

18°F

(10°K)

0°F

(0°K)

Start-stop of refrigeration

Using this setting, refrigeration can be started or stopped. Start and stop can also 

be accomplished with the external switch function on terminals 1 & 2 (see wiring 

section).

r12

0 (OFF)

1 (ON)

1

Thermostat function for controlling a liquid line solenoid valve

0:  No thermostat function. Only superheat is regulated. 

1:  Thermostat function enabled in addition to superheat regulation.

r14

0 (OFF)

1 (ON)

0 (OFF)

Survey of functions, settings, and parameters

Regulating settings

 

Alarm for high temperature (sensor S3).

When S3 temperature exceeds reference plus this differential temperature setting, 

the alarm is activated. Note that there may be an alarm delay (A03). Reference can 

be seen in u28. 

A01

5.4°F

(3°K)

36°F

(20°K)

9°F

(5.0°K)

Alarm for low temperature (sensor S3).

When S3 temperature is lower than reference minus this differential temperature 

setting, the alarm is activated. Note that there may be an alarm delay (A03). 

Reference can be seen in u28. 

A02

1.8°F

(1°K)

18°F

(10°K)

5.4°F

(3.0°K)

Alarm delay

If this parameter is set, a timer is activated when one of the two alarm settings is 

exceeded. The alarm is generated only after the time delay has passed. 

A03

0 (min.)

90 (min.)

30 

(min.)

Alarms

The controller is capable of generating alarms. When there is an alarm, the three lower  
LEDs on the front panel will flash and the alarm relay will cut in. 

Содержание EKC 315A

Страница 1: ...Manual REFRIGERATION AND AIR CONDITIONING Superheat controller EKC 315A...

Страница 2: ...ring 3 Operating principle 3 Operating the EKC 315A 4 5 Quick Setup Guide 6 Survey of functions settings and parameters 7 10 Service parameters for troubleshooting 11 Technical data 11 Wiring diagram...

Страница 3: ...ively small refrigerant charge the type ICM valve is recommended In systems with an AKV A valve the capacity can be distributed by using up to three valves in parallel When using more than one AKV A p...

Страница 4: ...r an error in regulation In this situation pushing the upper button for 1 second will cause the alarm or error code to be displayed When an alarm code is displayed by pushing the upper button the alar...

Страница 5: ...parameter you have scrolled to Press the both buttons simultaneously To increase the setting Press the upper button To decrease the setting Press the lower button To save the new setting and return to...

Страница 6: ...actuator s default settings input setting 2 Enter the pressure transmitters working range in parameters o20 min value and o21 max value Note These settings must be entered in gauge pressure and most t...

Страница 7: ...for example for loss due to a long sensor cable r09 18 F 10 K 18 F 10 K 0 F 0 K Offset of temperature sensor S3 signal To calibrate the sensor reading or to compensate for example for loss due to a lo...

Страница 8: ...half n19 0 2 1 0 0 3 Amplification factor for superheat only in 1 1 systems This setting determines the ICM or AKV valve s opening degree as a function of the change in evaporating pressure An increas...

Страница 9: ...fset At maximum AI the offset will be as set in parameter r06 o10 0 4 0 Frequency Must be set to the frequency of the 24 Vac power source o12 0 50 Hz 1 60 Hz 0 50 Hz Selection of normal display conten...

Страница 10: ...F 35 C Value of analog output at maximum current terminals 2 5 only applicable to AKV A or TQ Upper end of temperature or opening degree range that will yield a current output of 20 mA o28 94 F 70 C 3...

Страница 11: ...ctive complied and EMC demands re CE marking complied with LVD tested according to EN 60730 1 and EN 60730 2 9 EMC tested according to EN50081 1and EN 50082 2 Service Parameters for Troubleshooting vi...

Страница 12: ...tional power source needed Terminal pairs Description 17 18 Signal from TQ discontinued valve actuator See Appendix 1 for TQ wiring diagram 18 19 Optional current input from PLC or other source for of...

Страница 13: ...er than the integration time Tn parameter n05 time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1 2 times Tp 2 Wait until the system is in balance again 3 If there is still oscillation reduce Kp initi...

Страница 14: ...o types of superheat regulation load defined control and adaptive control are shown below For industrial refrigeration applications load defined control should be tried first Load defined superheat Th...

Страница 15: ...Manual EKC 315A Industrial Evaporator Controller 15 USCO PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008...

Страница 16: ...O PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008 Danfoss Inc Refrigeration Air Conditioning Division 7941 Corporate Drive Baltimore MD 21236 Ph 410 931 8250 Fax 410 931 8256 E mail baltimore danfo...

Отзывы: