background image

Manual 

EKC 315A  Industrial Evaporator Controller 

 

USCO.PD.RD0.A1.22 / 521U0092

 

© Danfoss USCO (HMR_MKS), 04-2008

Description of setting

Parameter Minimum Maximum

Factory 

setting

Field 

setting

P:  Amplification factor, K

p

Increasing proportional factory Kp leads to larger changes in controller output for a given 

input (regulation becomes faster).   Too high a K

can cause the valve to hunt. 

n04

0.5

20

3.0

I:  Integration time T

n

 

 

Decreasing T

n

 results in faster response to sensor value changes.

n05

30 (sec)

600 (sec)

120 (sec)

D:  Differentiation time T

d

This setting can be turned off by setting its value to minimum (0). Increasing Td increases 

controller output changes, but can lead to instability.

n06

0 (sec)

90 (sec)

0 (sec)

Maximum value for superheat reference

n09

4°F

(2°K)

90°F

(50°K)

10.8°F

(6°K)

Minimum value for superheat reference

WARNING: Due to the risk of liquid floodback, the setting should not be lower than 

approximately 4 - 7°F (2 -4°K).  

n10

2°F

(1°K)

22°F

(12°K)

7°F

(4°K)

MOP

If MOP function is not desired, adjust to maximum setting. MOP function limits valve 

opening degree as long as evaporating pressure is higher than user-set value.

n11

0 psig

(0 bar)

870 psig

(60 bar)

870 psig

(60 bar)

Period time for AKV and AKVA pulse valves

In  most cases, this parameter should not need to be changed.

 This parameter determines 

the length of the control period. The valve is opened for a certain percentage of each 

successive period. For example, when full valve capacity is called for, the valve will be 

opened for the entire period. When 60% valve capacity is required, the valve will be 

opened for 60% of the period. The control algorithm computes the capacity required for 

each period. 

n13

3 (sec)

10 (sec)

6 (sec)

Stability factor for superheat regulation

This value should only be changed by specially trained service technicians.

 A higher value will 

allow greater superheat fluctuation before the reference is changed.  

n18

0

10

5

Damping of amplification near the reference value

This value should only be changed by specially trained service technicians. 

This setting damps 

Kp near the reference value. A setting of 0.5 will reduce Kp by half. 

n19

0.2

1.0

0.3

Amplification factor for superheat (only in 1:1 systems)

This setting determines the ICM or AKV valve’s opening degree as a function of the change 

in evaporating pressure. An increase in evaporating pressure will result in a lower opening 

degree. When there is a drop-out on the low pressure thermostat during start-up, the 

value must be raised. If there is pendling during start-up, the value must be reduced a 

small amount.  This value should only be changed by specially trained service technicians. 

n20

0.0

10.0

0.4

Defines superheat regulation 

(see Appendix 2

)

1) Minimum stable superheat (MSS). Adaptive regulation.

2) (Works best for industrial refrigeration systems) Based on Load-defined superheat. The 

reference is established based on the line formed by the three points: n09, n10, and n22.  

n21

1

2

1

Value of minimum superheat reference for loads under 10%

The value must be less than n10. The controller will force the valve closed when superheat 

is below this set value. 

n22

1

15

2

Standby TQ valve (discontinued valve) temperature when valve closed

The TQ actuator is kept warm when the valve closes. As the closing point can not be 

defined exactly due to tolerances and pressure variations, the setting can be changed as 

needed to affect valve closing tightness.

n26

-27°F

(-15°K)

36°F

(20°K)

0°F

(0°K)

Standby TQ valve (discontinued valve) temperature when valve open

The TQ actuator’s temperature is kept low when the valve reaches its fully open position. 

This parameter sets the number of degrees that the temperature is to be above the 

expected open temperature when the valve is completely open. A greater value ensures 

that the valve is open, but a greater value will also result in slower closing.

n27

-27°F

(-15°K)

126°F

(70°K)

36°F

(20°K)

Maximum opening degree

The ICM or AKV valve’s opening degree can be limited. The value is set in %. This value 

should only be changed by specially trained service technicians. 

n32

0 (%)

100 (%)

100 (%)

Minimum opening degree

This value should only be changed by specially trained service technicians.

 The ICM or AKV 

valve’s opening degree can be set to a minimum valve that disables full closure. 

n33

0 (%)

100 (%)

0 (%)

Regulating parameters

NOTE: Only a trained Danfoss technician should adjust settings given in the gray blocks. Misadjustment could cause serious 

system malfunction.

Содержание EKC 315A

Страница 1: ...Manual REFRIGERATION AND AIR CONDITIONING Superheat controller EKC 315A...

Страница 2: ...ring 3 Operating principle 3 Operating the EKC 315A 4 5 Quick Setup Guide 6 Survey of functions settings and parameters 7 10 Service parameters for troubleshooting 11 Technical data 11 Wiring diagram...

Страница 3: ...ively small refrigerant charge the type ICM valve is recommended In systems with an AKV A valve the capacity can be distributed by using up to three valves in parallel When using more than one AKV A p...

Страница 4: ...r an error in regulation In this situation pushing the upper button for 1 second will cause the alarm or error code to be displayed When an alarm code is displayed by pushing the upper button the alar...

Страница 5: ...parameter you have scrolled to Press the both buttons simultaneously To increase the setting Press the upper button To decrease the setting Press the lower button To save the new setting and return to...

Страница 6: ...actuator s default settings input setting 2 Enter the pressure transmitters working range in parameters o20 min value and o21 max value Note These settings must be entered in gauge pressure and most t...

Страница 7: ...for example for loss due to a long sensor cable r09 18 F 10 K 18 F 10 K 0 F 0 K Offset of temperature sensor S3 signal To calibrate the sensor reading or to compensate for example for loss due to a lo...

Страница 8: ...half n19 0 2 1 0 0 3 Amplification factor for superheat only in 1 1 systems This setting determines the ICM or AKV valve s opening degree as a function of the change in evaporating pressure An increas...

Страница 9: ...fset At maximum AI the offset will be as set in parameter r06 o10 0 4 0 Frequency Must be set to the frequency of the 24 Vac power source o12 0 50 Hz 1 60 Hz 0 50 Hz Selection of normal display conten...

Страница 10: ...F 35 C Value of analog output at maximum current terminals 2 5 only applicable to AKV A or TQ Upper end of temperature or opening degree range that will yield a current output of 20 mA o28 94 F 70 C 3...

Страница 11: ...ctive complied and EMC demands re CE marking complied with LVD tested according to EN 60730 1 and EN 60730 2 9 EMC tested according to EN50081 1and EN 50082 2 Service Parameters for Troubleshooting vi...

Страница 12: ...tional power source needed Terminal pairs Description 17 18 Signal from TQ discontinued valve actuator See Appendix 1 for TQ wiring diagram 18 19 Optional current input from PLC or other source for of...

Страница 13: ...er than the integration time Tn parameter n05 time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1 2 times Tp 2 Wait until the system is in balance again 3 If there is still oscillation reduce Kp initi...

Страница 14: ...o types of superheat regulation load defined control and adaptive control are shown below For industrial refrigeration applications load defined control should be tried first Load defined superheat Th...

Страница 15: ...Manual EKC 315A Industrial Evaporator Controller 15 USCO PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008...

Страница 16: ...O PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008 Danfoss Inc Refrigeration Air Conditioning Division 7941 Corporate Drive Baltimore MD 21236 Ph 410 931 8250 Fax 410 931 8256 E mail baltimore danfo...

Отзывы: