background image

Manual 

 

 

EKC 315A Industrial Evaporator Controller 

 

© Danfoss USCO (HMR_MKS), 04-2008

 

 

USCO.PD.RD0.A1.22 /521U0092 

3

Introduction

The EKC 315A controller can be applied where there is a need for 
accurate control of superheat and temperature in refrigeration 
systems, for example:

• Air coolers
• Process water chillers
• Air conditioning systems

Advantages

The evaporator is optimally charged, even when there are great 

• 

variations in load and suction pressure. 
Energy savings -- adaptive regulation of refrigerant injection 

• 

ensures optimum utilization of the evaporator, resulting in a 
higher suction pressure. 
Using adaptive control, superheat is maintained at the minimum 

• 

stable level -- an energy-efficient way to optimize the evaporator  
while at the same time, media temperature is thermostatically 
controlled

Valve Compatibility

The EKC 315A can control evaporator superheat by means of one 
pressure transmitter and one temperature sensor using either an ICM 
motorized modulating valve with ICAD motor actuator or an AKV or 
AKVA pulse-width-modulating expansion valve.

 

In systems where there is one evaporator, one compressor, and one 
condenser, and a relatively small refrigerant charge, the type ICM 
valve is recommended. 

In systems with an AKV/A valve, the capacity can be distributed 
by using up to three valves in parallel. When using more than one 
AKV/A per evaporator, an EKC 347 controller is required for each 
additional AKV/A in the master-slave configuration. The controller 
will generate pulses to the multiple valves in such a way that they 
will not be pulsed simultaneously. 

Features and Functions

Superheat regulation

• 

Temperature control via thermostat function

• 

MOP function (limits valve opening degree as long as evaporating 

• 

pressure is higher than user-set value)
ON-OFF input for start-stop of regulation

• 

Input signal that can offset the superheat reference or the 

• 

temperature reference.
Capable of generating alarms if user-set limits are exceeded

• 

Relay output for solenoid valve control

• 

PID regulation

• 

Analog output to either (a) control an ICM motorized valve; or (b) 

• 

to monitor superheat, valve opening degree of an AKVA, or air 
temperature. 

 

Operation

Type

Function

Code No.

EKC 315A

Industrial evaporator controller

084B7086

Ordering

Superheat control with thermostat function

The superheat is controlled by pressure transmitter P and 

temperature sensor S2.  The temperature is controlled by the 

solenoid valve, the thermostat setting, and the temperature 

sensor S3 in the return air.

Содержание EKC 315A

Страница 1: ...Manual REFRIGERATION AND AIR CONDITIONING Superheat controller EKC 315A...

Страница 2: ...ring 3 Operating principle 3 Operating the EKC 315A 4 5 Quick Setup Guide 6 Survey of functions settings and parameters 7 10 Service parameters for troubleshooting 11 Technical data 11 Wiring diagram...

Страница 3: ...ively small refrigerant charge the type ICM valve is recommended In systems with an AKV A valve the capacity can be distributed by using up to three valves in parallel When using more than one AKV A p...

Страница 4: ...r an error in regulation In this situation pushing the upper button for 1 second will cause the alarm or error code to be displayed When an alarm code is displayed by pushing the upper button the alar...

Страница 5: ...parameter you have scrolled to Press the both buttons simultaneously To increase the setting Press the upper button To decrease the setting Press the lower button To save the new setting and return to...

Страница 6: ...actuator s default settings input setting 2 Enter the pressure transmitters working range in parameters o20 min value and o21 max value Note These settings must be entered in gauge pressure and most t...

Страница 7: ...for example for loss due to a long sensor cable r09 18 F 10 K 18 F 10 K 0 F 0 K Offset of temperature sensor S3 signal To calibrate the sensor reading or to compensate for example for loss due to a lo...

Страница 8: ...half n19 0 2 1 0 0 3 Amplification factor for superheat only in 1 1 systems This setting determines the ICM or AKV valve s opening degree as a function of the change in evaporating pressure An increas...

Страница 9: ...fset At maximum AI the offset will be as set in parameter r06 o10 0 4 0 Frequency Must be set to the frequency of the 24 Vac power source o12 0 50 Hz 1 60 Hz 0 50 Hz Selection of normal display conten...

Страница 10: ...F 35 C Value of analog output at maximum current terminals 2 5 only applicable to AKV A or TQ Upper end of temperature or opening degree range that will yield a current output of 20 mA o28 94 F 70 C 3...

Страница 11: ...ctive complied and EMC demands re CE marking complied with LVD tested according to EN 60730 1 and EN 60730 2 9 EMC tested according to EN50081 1and EN 50082 2 Service Parameters for Troubleshooting vi...

Страница 12: ...tional power source needed Terminal pairs Description 17 18 Signal from TQ discontinued valve actuator See Appendix 1 for TQ wiring diagram 18 19 Optional current input from PLC or other source for of...

Страница 13: ...er than the integration time Tn parameter n05 time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1 2 times Tp 2 Wait until the system is in balance again 3 If there is still oscillation reduce Kp initi...

Страница 14: ...o types of superheat regulation load defined control and adaptive control are shown below For industrial refrigeration applications load defined control should be tried first Load defined superheat Th...

Страница 15: ...Manual EKC 315A Industrial Evaporator Controller 15 USCO PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008...

Страница 16: ...O PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008 Danfoss Inc Refrigeration Air Conditioning Division 7941 Corporate Drive Baltimore MD 21236 Ph 410 931 8250 Fax 410 931 8256 E mail baltimore danfo...

Отзывы: