background image

Manual 

EKC 315A  Industrial Evaporator Controller 

12 

 

USCO.PD.RD0.A1.22 / 521U0092

 

© Danfoss USCO (HMR_MKS), 04-2008

Wiring diagram and terminal functions

Terminal 

pairs

Description

1-2

Switch function for start-stop of regulation. When there 

is no connections between terminals 1 & 2, the controller 

will send a signal to close the valve. 

If not using a switch, 

terminals must be shorted with a jumper wire.

2-5

Current output that is used:

To  control    a  motorized  valve  type  ICM with  ICAD 

1. 

motor actuator, or

For  remote  monitoring  when  the  ICM/ICAD  is  not 

2. 

used (see parameter o09).

9-10

Optional relay output for control of a liquid line solenoid 

valve. Control is based on thermostat setting. The relay 

is closed on power failure.

12-13

Alarm relay. There is no connection between 12 and 

13 during alarm conditions or when the controller is 

not functioning.

14-15

Pressure transmitter, type AKS 33 or equivalent. Note: 

controller powers the 4-20 mA loop (no additional 

power source needed.

Terminal 

pairs

Description

17-18

Signal from TQ (discontinued valve actuator. See 

Appendix 1 for TQ wiring diagram).

18-19

Optional current input from PLC or other source, 

for offsetting the thermostat setting or superheat 

reference.

20-21

Temperature sensor S2 (PT 1000) at evaporator outlet 

for superheat.

21-22

Temperature sensor S3 (PT 1000) for thermostat 

function controlling a liquid line solenoid valve.

23-24

24 Vac output for control of pulse width modulated 

valve type AKV/A (Maximum 20Ws coil). Can also be 

used to power the discontinued type TQ valve (see 

Appendix 1 for TQ wiring diagram.

25-26

Supply voltage 24 Vac. 80 VA maximum load 

depending on valve

Green (-)

Brown (+)

24Vd.c.

Yellow (-)

Grey (+)

Solenoid 

relay

Alarm 

relay

Optional analog
input from PLC etc.

AKV or AKVA pulse-width 
modulation expansion valve
Note: controller powers the 
24Va.c., max 20W coil

Pressure transmitter, 
type AKS 33

Motorized modulating valve, type 
ICM/ICAD, must be supplied with 
24Vd.c. from an external source.

80 VA max load

Note: Each  EKC 315A controller can 
control a type AKV/A valve or an ICM, 
but not both simultaneously.

Содержание EKC 315A

Страница 1: ...Manual REFRIGERATION AND AIR CONDITIONING Superheat controller EKC 315A...

Страница 2: ...ring 3 Operating principle 3 Operating the EKC 315A 4 5 Quick Setup Guide 6 Survey of functions settings and parameters 7 10 Service parameters for troubleshooting 11 Technical data 11 Wiring diagram...

Страница 3: ...ively small refrigerant charge the type ICM valve is recommended In systems with an AKV A valve the capacity can be distributed by using up to three valves in parallel When using more than one AKV A p...

Страница 4: ...r an error in regulation In this situation pushing the upper button for 1 second will cause the alarm or error code to be displayed When an alarm code is displayed by pushing the upper button the alar...

Страница 5: ...parameter you have scrolled to Press the both buttons simultaneously To increase the setting Press the upper button To decrease the setting Press the lower button To save the new setting and return to...

Страница 6: ...actuator s default settings input setting 2 Enter the pressure transmitters working range in parameters o20 min value and o21 max value Note These settings must be entered in gauge pressure and most t...

Страница 7: ...for example for loss due to a long sensor cable r09 18 F 10 K 18 F 10 K 0 F 0 K Offset of temperature sensor S3 signal To calibrate the sensor reading or to compensate for example for loss due to a lo...

Страница 8: ...half n19 0 2 1 0 0 3 Amplification factor for superheat only in 1 1 systems This setting determines the ICM or AKV valve s opening degree as a function of the change in evaporating pressure An increas...

Страница 9: ...fset At maximum AI the offset will be as set in parameter r06 o10 0 4 0 Frequency Must be set to the frequency of the 24 Vac power source o12 0 50 Hz 1 60 Hz 0 50 Hz Selection of normal display conten...

Страница 10: ...F 35 C Value of analog output at maximum current terminals 2 5 only applicable to AKV A or TQ Upper end of temperature or opening degree range that will yield a current output of 20 mA o28 94 F 70 C 3...

Страница 11: ...ctive complied and EMC demands re CE marking complied with LVD tested according to EN 60730 1 and EN 60730 2 9 EMC tested according to EN50081 1and EN 50082 2 Service Parameters for Troubleshooting vi...

Страница 12: ...tional power source needed Terminal pairs Description 17 18 Signal from TQ discontinued valve actuator See Appendix 1 for TQ wiring diagram 18 19 Optional current input from PLC or other source for of...

Страница 13: ...er than the integration time Tn parameter n05 time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1 2 times Tp 2 Wait until the system is in balance again 3 If there is still oscillation reduce Kp initi...

Страница 14: ...o types of superheat regulation load defined control and adaptive control are shown below For industrial refrigeration applications load defined control should be tried first Load defined superheat Th...

Страница 15: ...Manual EKC 315A Industrial Evaporator Controller 15 USCO PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008...

Страница 16: ...O PD RD0 A1 22 521U0092 Danfoss USCO HMR_MKS 04 2008 Danfoss Inc Refrigeration Air Conditioning Division 7941 Corporate Drive Baltimore MD 21236 Ph 410 931 8250 Fax 410 931 8256 E mail baltimore danfo...

Отзывы: