Installation Guide
ECL Comfort 310, application A376
7.6 Anti-bacteria
On selected days during the week the DHW temperature can
be increased in order to neutralize bacteria in the DHW system.
The desired DHW temperature 'Desired T' (typically 80 °C) will be
present for the selected day(s) and duration.
The anti-bacteria function is not active in frost protection mode.
Desired temp.
° C
80
55
Time
Day / start time
Duration
During the anti-bacteria process, the return temperature limitation is
not active.
Day
Circuit
Setting range
Factory setting
3
Weekdays
Select (mark) the day(s) of the week where the anti-bacteria function must
be active.
M = Monday
T
= Tuesday
W = Wednesday
T
= Thursday
F
= Friday
S
= Saturday
S
= Sunday