Installation Guide
ECL Comfort 310, application A376
5.6 Control parameters
Motor pr. (motor protection)
11174
Circuit
Setting range
Factory setting
1
OFF / 10 ... 59 m
OFF
Prevents the controller from unstable temperature control (and resulting
actuator oscillations). This can occur at very low load. The motor protection
increases the lifetime of all involved components.
OFF:
Motor protection is not activated.
10 ... 59:
Motor protection is activated after the set activation
delay in minutes.
Recommended for heating systems with variable load.
Xp (proportional band)
11184
Circuit
Setting range
Factory setting
1
5 ... 250 K
80 K
Set the proportional band. A higher value will result in a stable but
slow control of the flow temperature.
Xp (proportional band) — A376.9
11184
Circuit
Setting range
Factory setting
1
5 ... 250 K
85 K
Set the proportional band. A higher value will result in a stable but
slow control of the flow temperature.
Tn (integration time constant)
11185
Circuit
Setting range
Factory setting
1
1 ... 999 s
30 s
Set a high integration time constant (in seconds) to obtain a slow
but stable reaction to deviations.
A low integration time constant will make the controller react fast
but with less stability.
Tn (integration time constant) — A376.9
11185
Circuit
Setting range
Factory setting
1
1 ... 999 s
25 s
Set a high integration time constant (in seconds) to obtain a slow
but stable reaction to deviations.
A low integration time constant will make the controller react fast
but with less stability.
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK
89