Installation Guide
ECL Comfort 310, application A376
7.5 Application
Send desired T
13500
Circuit
Setting range
Factory setting
3
OFF / ON
ON
When the controller acts as a slave controller in a master / slave system,
information about the desired flow temperature can be sent to the master
controller via the ECL 485 bus.
OFF:
Information about the desired flow temperature is not
sent to the master controller.
ON:
Information about the desired flow temperature is sent
to the master controller.
In the master controller, 'Demand offset' must be set to a value in order
to react on a desired flow temperature from a slave controller.
P exercise (pump exercise)
13022
Circuit
Setting range
Factory setting
3
OFF / ON
ON
Exercises the pump to avoid blocking in periods without heat demand.
OFF:
The pump exercise is not active.
ON:
The pump is switched ON for 1 minute every third day at
noon (12:14 hours).
M exercise (valve exercise)
13023
Circuit
Setting range
Factory setting
3
OFF / ON
OFF
Exercises the valve to avoid blocking in periods without heat demand.
OFF:
The valve exercise is not active.
ON:
The valve opens for 7 minutes and closes for 7 minutes
every third day at noon (12:00 hours).
P frost T
13077
Circuit
Setting range
Factory setting
3
OFF / -10 ... 20 °C
2 °C
When the outdoor temperature is below the set temperature in ‘P frost T’,
the controller automatically switches ON the circulation pump to protect
the system.
OFF:
No frost protection.
-10 ... 20:
The circulation pump is ON when the outdoor
temperature is below the set value.
Under normal conditions, your system is not frost protected if your
setting is below 0 °C or OFF.
For water-based systems, a setting of 2 °C is recommended.
138