Installation Guide
ECL Comfort 310, application A376
Setting
ID
Page
Factory settings in circuit(s)
1
2
3
Nz (neutral zone)
11187
90
3 K
Nz (neutral zone) — A376.9
11187
90
2 K
Min. act. time (min. activation time gear motor)
11189
91
10
ECA addr. (choice of Remote Control Unit)
11010
93
OFF
Demand offset
11017
93
OFF
P demand
11050
93
OFF
Send desired T
11500
94
ON
P exercise (pump exercise)
11022
94
ON
M exercise (valve exercise)
11023
94
OFF
DHW priority (closed valve / normal operation)
11052
94
OFF
P frost T
11077
95
2 °C
P heat T (heat demand)
11078
95
20 °C
P post-run
11040
95
3 m
Frost pr. T (frost protection temperature)
11093
95
10 °C
Ext. input (external override) — ECL 310
11141
96
OFF
Ext. mode (external override mode)
11142
96
COM-
FORT
Upper difference
11147
97
OFF
Lower difference
11148
97
OFF
Delay
11149
98
10 m
Lowest temp.
11150
98
30 °C
Alarm overview, in general
98
S7 pressure — A376.9
98
Alarm high — A376.9
11614
99
2.3
Alarm low — A376.9
11615
99
0.0
Alarm time-out — A376.9
11617
99
30 s
Digital S8 — A376.9
99
Alarm value — A376.9
11636
99
0
Alarm time-out — A376.9
11637
99
30 s
Max. temp. — A376.9
99
Max. flow T— A376.9
11079
100
90 °C
Delay — A376.9
11180
100
60 s
Heat curve
101
1.0
Temp. max. (flow temp. limit, max.)
12178
102
90 °C
Temp. min. (flow temp. limit, min.)
12177
102
10 °C
Adapt. time (adaption time)
12015
103
OFF
Infl. - max. (room temp. limitation, max.)
12182
104
-4.0
Infl. - min. (room temp. limitation, min.)
12183
104
0.0
High T out X1 (return temp. limitation, high limit, X-axis)
12031
105
15 °C
Low limit Y1 (return temp. limitation, low limit, Y-axis)
12032
105
40 °C
Low T out X2 (return temp. limitation, low limit, X-axis)
12033
105
-15 °C
High limit Y2 (return temp. limitation, high limit, Y-axis)
12034
106
60 °C
Infl. - max. (return temp. limitation - max. influence)
12035
106
-2.0
Infl. - min. (return temp. limitation - min. influence)
12036
106
0.0
Adapt. time (adaptation time)
12037
106
25 s
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK
71