Installation Guide
ECL Comfort 310, application A376
Delay
13149
Circuit
Setting range
Factory setting
3
1 ... 99 m
10 m
If an alarm condition from either 'Upper difference' or 'Lower difference' is
present for a longer time than the set delay (in min.), the alarm function
is activated.
1 ... 99 m:
The alarm function will be activated if the alarm
condition remains after the set delay.
Temp.
Flow temp.
Alarm limit
Time
Delay
Lowest temp.
13150
Circuit
Setting range
Factory setting
3
10 ... 50 °C
30 °C
The alarm function will not be activated if the desired flow temperature
is lower than the set value.
If the cause of the alarm disappears, the alarm indication and output
also disappear.
Alarm overview, in general
Circuit
Setting range
Factory setting
3
Access to overview showing the alarm number / alarm type. The alarm
number is entered into the alarm register and can be obtained from a
SCADA system.
Example: "3: Temp. monitor": If an alarm is activated because of conditions
in 'Temp. monitor' the alarm number 3 is placed in the alarm register.
Digital S16 — A376.9
Circuit
Setting range
Factory setting
3
Access to settings related to alarm input S16.
Alarm value — A376.9
13636
Circuit
Setting range
Factory setting
3
0 / 1
0
The alarm is based on a digital input applied to S16.
0:
The alarm function is active when a switch is closed.
1:
The alarm function is active when a switch is open.
Alarm time-out — A376.9
13637
Circuit
Setting range
Factory setting
3
0 ... 240 s
30 s
The alarm is activated when the switch has been closed or opened for a
longer time (in seconds) than the set value.
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK