Installation Guide
ECL Comfort 310, application A376
3.2 Understanding the controller display
Choosing a favorite display
Your favorite display is the display you have chosen as the default
display. The favorite display will give you a quick overview of the
temperatures or units that you want to monitor in general.
If the dial has not been activated for 20 min., the controller will
revert to the overview display you have chosen as favorite.
To shift between displays: Turn the dial until you reach the display
selector (
) at the bottom right side of the display. Push the dial and
turn to choose your favorite overview display. Push the dial again.
Heating circuit
Overview display 1 informs about:
actual outdoor temperature, controller mode,
actual room temperature, desired room temperature.
Overview display 2 informs about:
actual outdoor temperature, trend in outdoor temperature,
controller mode, max. and min. outdoor temperatures since
midnight as well as desired room temperature.
Overview display 3 informs about:
date, actual outdoor temperature, controller mode, time, desired
room temperature as well as shows the comfort schedule of the
current day.
Overview display 4 informs about:
state of the controlled components, actual flow temperature,
(desired flow temperature), controller mode, return temperature
(limitation value).
Dependent on the chosen display, the overview displays for the
heating circuit inform you about:
• actual outdoor temperature (-0.5)
• controller mode ( )
• actual room temperature (24.5)
• desired room temperature (20.7 °C)
• trend in outdoor temperature ( )
• min. and max. outdoor temperatures since midnight ( )
• date (23.02.2010)
• time (7:43)
• comfort schedule of the current day (0 - 12 - 24)
• state of the controlled components (M2, P2)
• actual flow temperature (49 °C), (desired flow temperature (31))
• return temperature (24 °C) (limitation temperature (50))
Overview display 1:
Overview display 2:
Overview display 3:
Overview display 4:
The setting of the desired room temperature is important even if a
room temperature sensor / Remote Control Unit is not connected.
If the temperature value is displayed as
"- -" the sensor in question is not connected.
"- - -" the sensor connection is short-circuited.
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK
61