Installation Guide
ECL Comfort 310, application A376
Infl. - min. (room temp. limitation, min.)
11183
Circuit
Setting range
Factory setting
1
0.0 .... 9.9
0.0
Determines how much the desired flow temperature will be influenced
(increased) if the actual room temperature is lower than the desired room
temperature (P control).
0.0:
The room temperature has no influence.
9.9:
The room temperature has a big influence.
Adapt. time (adaption time)
11015
Circuit
Setting range
Factory setting
1
OFF / 1 ... 50 s
OFF
Controls how fast the actual room temperature adapts to the desired room
temperature (I control).
OFF:
The control function is not influenced by the 'Adapt.
time'.
1:
The desired room temperature is adapted quickly.
50:
The desired room temperature is adapted slowly.
The adaptation function can correct the desired flow temperature
with max. 8 K x heat curve value.
78
DEN-SMT/DK
VI.GU.B1.02
Danfoss District Energy