Installation Guide
ECL Comfort 310, application A376
4.0 Settings overview
It is recommendable to make a note of any changed settings in the empty columns.
Setting
ID
Page
Factory settings in circuit(s)
1
2
3
Heat curve
75
1.0
Temp. max. (flow temp. limit, max.)
11178
76
90 °C
Temp. min. (flow temp. limit, min.)
11177
76
10 °C
Infl. - max. (room temp. limitation, max.)
11182
77
-4.0
Infl. - min. (room temp. limitation, min.)
11183
78
0.0
Adapt. time (adaption time)
11015
78
OFF
High T out X1 (return temp. limitation, high limit, X-axis)
11031
79
15 °C
Low limit Y1 (return temp. limitation, low limit, Y-axis)
11032
79
40 °C
Low T out X2 (return temp. limitation, low limit, X-axis)
11033
79
-15 °C
High limit Y2 (return temp. limitation, high limit, Y-axis)
11034
80
60 °C
Infl. - max. (return temp. limitation - max. influence)
11035
80
-2.0
Infl. - max. (return temp. limitation - max. influence) — A376.9
11035
80
0.0
Infl. - min. (return temp. limitation - min. influence)
11036
80
0.0
Adapt. time (adaptation time)
11037
81
25 s
Priority (priority for return temp. limitation)
11085
81
OFF
Actual (actual flow or power)
11110
82
Actual limit (limitation value)
11111
82
High T out X1 (flow / power limitation, high limit, X-axis)
11119
82
15 °C
Low limit Y1 (flow / power limitation, low limit, Y-axis)
11117
83
999.9
l/h
Low T out X2 (flow / power limitation, low limit, X-axis)
11118
83
-15 °C
High limit Y2 (flow / power limitation, high limit, Y-axis)
11116
83
999.9
l/h
Adapt. time (adaptation time)
11112
83
OFF
Filter constant
11113
83
10
Input type
11109
84
OFF
Units
11115
84
l/h
Auto saving (saving temp. dependent on outdoor temp.)
11011
85
-15 °C
Boost
11012
85
OFF
Ramp (reference ramping)
11013
86
OFF
Optimizer (optimizing time constant)
11014
86
OFF
Pre-stop (optimized stop time)
11026
87
ON
Based on (optimization based on room / outdoor temp.)
11020
87
OUT
Total stop
11021
87
OFF
Cut-out (limit for heating cut-out)
11179
88
20 °C
Parallel operation
11043
88
OFF
Motor pr. (motor protection)
11174
89
OFF
Xp (proportional band)
11184
89
80 K
Xp (proportional band) — A376.9
11184
89
85 K
Tn (integration time constant)
11185
89
30 s
Tn (integration time constant) — A376.9
11185
89
25 s
M run (running time of the motorized control valve)
11186
90
30 s
M run (running time of the motorized control valve) — A376.9
11186
90
120 s