Installation Guide
ECL Comfort 310, application A376
5.7 Application
ECA addr. (choice of Remote Control Unit)
11010
Circuit
Setting range
Factory setting
1
OFF / A / B
OFF
Decides the communication with the Remote Control Unit.
OFF:
No Remote Control Unit. Only room temperature sensor,
if any.
A:
Remote Control Unit ECA 30 / 31 with address A.
B:
Remote Control Unit ECA 30 / 31 with address B.
The Remote Control Unit has no influence on the DHW control.
The Remote Control Unit must be set accordingly (A or B).
Demand offset
11017
Circuit
Setting range
Factory setting
1
OFF / 1 ... 20 K
OFF
The desired flow temperature in heating circuit 1 can be influenced by the
demand for a desired flow temperature from another controller (slave) or
another circuit.
OFF:
The desired flow temperature in circuit 1 is not
influenced by the demand of any other controller (slave
or circuit 2).
1 ... 20:
The desired flow temperature is increased by the set
value in ‘Demand offset’, if the demand of the slave /
circuit 2 is higher.
Temp.
Setting in
‘Demand offset’
Des. flow temp.,
circuit 1
Des. flow temp.,
circuit 2
Time
The function of ‘Demand offset’ can compensate for heat losses
between master and slave controlled systems.
P demand
11050
Circuit
Setting range
Factory setting
1
OFF / ON
OFF
Choose conditions for the circulation pump in the heating circuit.
OFF:
The circulation pump is ON when the desired flow
temperature in the heating circuit is higher than the
value set in 'P heat T'.
ON:
The circulation pump is ON when the desired flow
temperature from slaves is higher than the value set in
'P heat T'.
The circulation pump is always controlled according to frost protection
conditions.