Service Settings
EY.65.H4.02
48
Room influence
These settings determine how the room temperature should influence flow tempera-
ture control. They are only applicable when a room sensor is connected in the heat
circuit.
Display text
Parameter
Default value,
range
Description
Max. ampli-
fic.
Maximum
amplification
Default value:
0.0 K
Range:
– 25.0 - 25.0
K
If the room temperature exceeds the
room temperature setpoint, the flow tem-
perature in the heat circuit will be re-
duced according to the Max. amplific.
setting
Min. amplific.
Minimum am-
plification
Default value:
0.0 K
Range:
– 25.0 - 25.0
K
If the room temperature falls below the
room temperature setpoint, the flow tem-
perature in the heat circuit will be in-
creased according to the Min. amplific.
setting
Adaptive
Default value:
OFF
Range:
ON, OFF
When the setting is ON, the flow tem-
perature is adjusted according to varia-
tions of the room temperature over a
period of time
!
Note:
When this setting is ON, the Max. am-
plific. and Min. amplific. settings should
be symmetrical with respect to 0, for
example, Max. amplific. = –3 K and
Min. amplific. = + 3 K
10.2.4 Limiter
This section describes the parameters you can set in pictures under the Limiter menu
item.
Return temperature
The following settings affect the return temperature limiter. See also page 47.
Display text
Parameter
Default value,
range
Description
Type
Type of limi-
tation
Default value:
MAX
Range:
MIN, MAX
Type of return temperature limitation
used: maximum or minimum. The flow
temperature is modified, when the return
temperature is either above the calcu-
lated setpoint or below it
Calc. setpoint
Calculated
setpoint
–
The setpoint for the return temperature,
calculated from the return temperature
curve. This parameter is read-only and
cannot be set
Содержание ECL 2000
Страница 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Страница 2: ......
Страница 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Страница 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Страница 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Страница 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Страница 88: ...Appendix B Service Menus EY 65 H4 02 82 B 2 Hot Water Service Menus 0 1 2 3 4 5 1 or or 2 or 3 4 or or...
Страница 89: ...Appendix B Service Menus EY 65 H4 02 83 B 3 Common Function Menus 0 1 2 3 4 5 1 2 etc 3 etc 4 etc...
Страница 90: ...Appendix B Service Menus EY 65 H4 02 84 B 3 Common Function Menus Cont 0 1 2 3 4 5 5 etc 6 7 8 9...
Страница 91: ...Appendix B Service Menus EY 65 H4 02 85 B 3 Common Function Menus Cont 0 1 2 3 4 5 10 11 or or 12 13...
Страница 92: ...Appendix B Service Menus EY 65 H4 02 86...
Страница 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Страница 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Страница 106: ...Index EY 65 H4 02 100...