Service Settings
EY.65.H4.02
43
Pre-heat period
This is the function that allows the controller to calculate the optimum starting time. If
the system is equipped with a room temperature sensor, this function is adaptive.
If no room temperature sensor is connected, the controller estimates the room tem-
perature as a function of the actual outdoor temperature and the default pre-heat pe-
riod entered by the operator (see below). Furthermore, if the system has been on night
setback for a long period, the controller increases the length of the pre-heat period. In
this way, the controller is able to compensate for fluctuations in outdoor temperature
and accumulated heat in buildings.
Display text
Parameter
Default value,
range
Description
Default
Default pre-
heat period
Default value:
23 hours
Range:
0-24 hours
As default, you must enter a pre-heat
period that you estimate is suitable given
the following conditions:
•
Outdoor temperature 0 °C
•
Actual room temperature 5 °C
•
Comfort temperature setting 20 °C
•
Flow temperature 80 °C during the
heating period
Max. limit
Maximum pre-
heat period
Default value:
0 hours
Range:
0-24 hours
The maximum pre-heat period the system
is allowed to calculate and use. Change
this setting to enable the optimizer func-
tion
Calculated
Calculated
pre-heat pe-
riod
Range:
0-24 hours
The pre-heat period calculated by the
controller using the actual outdoor tem-
perature. This parameter is read-only and
cannot be set
Cooling period
These settings enable the controller to calculate the cooling period, i.e. how soon the
plant can be switched to night setback temperature while still ensuring that the room
temperature only drops by 1 K before the pre-programmed night setback time.
Display text
Parameter
Default value,
range
Description
Default
Default cool-
ing period
Default value:
1 hour
Range:
0-24 hours
You must enter a default cooling period
corresponding to the following condi-
tions:
•
Outdoor temperature 0 °C
•
Actual room temperature 20 °C
•
Room temperature reduction = 1 K
Max. limit
Maximum
cooling period
Default value:
0 hours
Range:
0-24 hours
The maximum cooling period the system
is allowed to calculate and use. Change
this setting to enable the optimizer func-
tion
Calculated
Calculated
cooling period
Range:
0-24 hours
The cooling period calculated by the
controller using the actual outdoor tem-
perature. This parameter is read-only and
cannot be set
Содержание ECL 2000
Страница 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Страница 2: ......
Страница 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Страница 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Страница 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Страница 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Страница 88: ...Appendix B Service Menus EY 65 H4 02 82 B 2 Hot Water Service Menus 0 1 2 3 4 5 1 or or 2 or 3 4 or or...
Страница 89: ...Appendix B Service Menus EY 65 H4 02 83 B 3 Common Function Menus 0 1 2 3 4 5 1 2 etc 3 etc 4 etc...
Страница 90: ...Appendix B Service Menus EY 65 H4 02 84 B 3 Common Function Menus Cont 0 1 2 3 4 5 5 etc 6 7 8 9...
Страница 91: ...Appendix B Service Menus EY 65 H4 02 85 B 3 Common Function Menus Cont 0 1 2 3 4 5 10 11 or or 12 13...
Страница 92: ...Appendix B Service Menus EY 65 H4 02 86...
Страница 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Страница 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Страница 106: ...Index EY 65 H4 02 100...