Service Settings
EY.65.H4.02
50
Wind
This function requires that a wind velocity sensor is connected to the system. It in-
creases the flow temperature in the heat circuit if the wind velocity grows above the
setpoint.
Display text
Parameter
Default value,
range
Description
Setpoint
Default value:
10 m/s
Range:
0-50 m/s
When the wind velocity is above this
value, the calculated flow temperature
will be modified according to the ampli-
fication factor
Amplification
Default value:
0.1 K
Range:
–25.0 - 25.0 K
Amplification factor for modification of
calculated flow temperature caused by
wind velocity
A negative amplification causes a reduc-
tion of the calculated flow temperature, a
positive amplification causes an increase.
Normally, the amplification is positive
Sun
This function requires that a sun sensor is connected to the system. It reduces the flow
temperature in the heat circuit when the sun intensity rises above the setpoint.
Display text
Parameter
Default value,
range
Description
Setpoint
Default value:
100 W/m
2
Range:
0-999 W/m
2
When the sun intensity is above this
value, the calculated flow temperature
will be modified according to the ampli-
fication factor
Amplification
Default value:
–0.1 K
Range:
–25.0 - 25.0 K
Amplification factor for modification of
calculated flow temperature caused by
sun intensity
A negative amplification causes a reduc-
tion of the calculated flow temperature, a
positive amplification causes an increase.
Normally, the amplification is negative
Universal
This function allows you to set up a customized limiting function. How the limiter
will work depends on the type of sensor connected to the input. This function is ex-
tremely flexible and is used for very special applications.
Please refer to the ECL 2000 Technical Manual (ref. [3]) for documentation of the
Universal limiter.
Содержание ECL 2000
Страница 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Страница 2: ......
Страница 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Страница 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Страница 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Страница 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Страница 88: ...Appendix B Service Menus EY 65 H4 02 82 B 2 Hot Water Service Menus 0 1 2 3 4 5 1 or or 2 or 3 4 or or...
Страница 89: ...Appendix B Service Menus EY 65 H4 02 83 B 3 Common Function Menus 0 1 2 3 4 5 1 2 etc 3 etc 4 etc...
Страница 90: ...Appendix B Service Menus EY 65 H4 02 84 B 3 Common Function Menus Cont 0 1 2 3 4 5 5 etc 6 7 8 9...
Страница 91: ...Appendix B Service Menus EY 65 H4 02 85 B 3 Common Function Menus Cont 0 1 2 3 4 5 10 11 or or 12 13...
Страница 92: ...Appendix B Service Menus EY 65 H4 02 86...
Страница 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Страница 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Страница 106: ...Index EY 65 H4 02 100...