Service Settings
EY.65.H4.02
47
10.2.3 PI Constant Settings
This section describes the parameters you can set in pictures under the PI Constant
menu item.
Flow temp. control
This group of settings determine how the flow temperature is controlled. The follow-
ing parameters can be set:
Display text
Parameter
Default value,
range
Description
Neutr. zone
Neutral zone
Default value:
3 K
Range:
0-9 K
When the flow temperature lies within
the neutral zone, the valve motor is not
activated
P-band
Proportional
band
Default value:
70 K
Range:
1-99 K
Indicates the amplification in the control
loop. If the flow temperature deviates
from the reference temperature, the mo-
tor will be positioned proportionally to
the temperature deviation and the pro-
portional band setting
Integr. time
Integration
time
Default value:
20 seconds
Range:
0-999 seconds
In case of a constant control error signal,
the motor will have moved by an amount
equal to that caused by the P-band after
the integration time has elapsed
When the integration time is set to 0, the
integral action is disabled
Return temp. limiter
The controller can be set up to adjust the flow temperature if the actual return tem-
perature either:
•
Rises above the return temperature setpoint (maximum limiting)
or
•
Falls below the return temperature setpoint (minimum limiting).
The return temperature setpoint is calculated from the return temperature curve (see
page 23).
The following parameters can be set for this control function (see also page 48):
Display text
Parameter
Default value,
range
Description
Amplification
Default value:
– 0.3 K
Range:
– 25.0 - 25.0
K
Amplification for return limiter
Integr. time
Integration
time
Default value:
30 min.
Range:
0-200 min.
Integration time
Содержание ECL 2000
Страница 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Страница 2: ......
Страница 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Страница 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Страница 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Страница 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Страница 88: ...Appendix B Service Menus EY 65 H4 02 82 B 2 Hot Water Service Menus 0 1 2 3 4 5 1 or or 2 or 3 4 or or...
Страница 89: ...Appendix B Service Menus EY 65 H4 02 83 B 3 Common Function Menus 0 1 2 3 4 5 1 2 etc 3 etc 4 etc...
Страница 90: ...Appendix B Service Menus EY 65 H4 02 84 B 3 Common Function Menus Cont 0 1 2 3 4 5 5 etc 6 7 8 9...
Страница 91: ...Appendix B Service Menus EY 65 H4 02 85 B 3 Common Function Menus Cont 0 1 2 3 4 5 10 11 or or 12 13...
Страница 92: ...Appendix B Service Menus EY 65 H4 02 86...
Страница 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Страница 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Страница 106: ...Index EY 65 H4 02 100...