Service Settings
EY.65.H4.02
71
10.4.7 Sensors
Cut-off time constant
These constants are used for calculating the filtered temperature (see page 42). The
controller calculates filtered values of outdoor and/or room temperatures, depending
on what sensors are connected to the system.
Display text
Parameter
Default value,
range
Description
Tout circ. 1
Tout circ. 2
Outdoor tem-
perature, cir-
cuit 1 or 2
Default value:
4 h
Range:
1.0-50.0 h
Time constant for calculating filtered
outdoor temperature. The filtered tem-
perature is used to control summer cut-
off
Troom circ. 1
Troom circ. 2
Room tem-
perature, cir-
cuit 1 or 2
Default value:
1 h
Range:
1.0-50.0 h
Time constant for calculating filtered
room temperature. Used to control sum-
mer cut-off
Time constants
These time constants are used to convert the input signals received from sensors con-
nected to the system.
Note:
Sensor time constants concern Pt 1000, ESMF and 0–10 V sensors. Pulse and digital
sensors are not affected by the time constants. See page 30 for information on sensor
setup.
Display text
Parameter
Default value,
range
Description
S1, S2, etc.
Sensor 1, sen-
sor 2, etc.
Default value:
Depends on
the type of
sensor used
Range:
0-999 seconds
or
0-200 minutes
Time constants for sensor inputs
The range 0-200 minutes is for outdoor
temperature sensors
Содержание ECL 2000
Страница 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Страница 2: ......
Страница 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Страница 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Страница 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Страница 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Страница 88: ...Appendix B Service Menus EY 65 H4 02 82 B 2 Hot Water Service Menus 0 1 2 3 4 5 1 or or 2 or 3 4 or or...
Страница 89: ...Appendix B Service Menus EY 65 H4 02 83 B 3 Common Function Menus 0 1 2 3 4 5 1 2 etc 3 etc 4 etc...
Страница 90: ...Appendix B Service Menus EY 65 H4 02 84 B 3 Common Function Menus Cont 0 1 2 3 4 5 5 etc 6 7 8 9...
Страница 91: ...Appendix B Service Menus EY 65 H4 02 85 B 3 Common Function Menus Cont 0 1 2 3 4 5 10 11 or or 12 13...
Страница 92: ...Appendix B Service Menus EY 65 H4 02 86...
Страница 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Страница 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Страница 106: ...Index EY 65 H4 02 100...