Service Settings
EY.65.H4.02
42
The diagram in Figure 4 illustrates the summer cut-off function. When the measured
outdoor or room temperature exceeds the setpoint (Outdoor temp. or Room temp.
setting) by 0.5 K, the flow temperature is reduced. The night setback level is main-
tained until the filtered outdoor/room temperature drops below the setpoint – 0.5 K.
See page 71 for information on setting parameters for calculating the filtered tem-
perature.
[Hours]
Plant switched off
Filtered temperature
Temperature
Measured temperature
Time
}
1K
°C
20
18
16
Figure 4. The summer cut-off function
Optimizer
The purpose of the ECL 2000’s Optimizer function is to help run the plant in the most
economic manner possible. The Optimizer offers functions for:
•
Calculating the optimum starting time in order for room temperature to reach the
desired level (the comfort temperature) at the time defined in the 7-day plan.
•
Calculating how much ahead of time the system can be switched to night setback
temperature, making sure, however, that the room temperature does not drop by
more than 1 K before the pre-programmed night-setback time.
•
Selecting the optimum method for pre-heating the system.
Settings for the optimizer are described on the following pages.
By default, the Optimizer functions are disabled. This has been accomplished by set-
ting the parameters Pre-heat period: Max. limit and Cooling period: Max. limit to
0 hours. The Optimizer functions can be enabled by changing these settings as indi-
cated on page 43. Optimizer heating and cooling can be enabled/disabled separately.
Содержание ECL 2000
Страница 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Страница 2: ......
Страница 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Страница 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Страница 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Страница 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Страница 88: ...Appendix B Service Menus EY 65 H4 02 82 B 2 Hot Water Service Menus 0 1 2 3 4 5 1 or or 2 or 3 4 or or...
Страница 89: ...Appendix B Service Menus EY 65 H4 02 83 B 3 Common Function Menus 0 1 2 3 4 5 1 2 etc 3 etc 4 etc...
Страница 90: ...Appendix B Service Menus EY 65 H4 02 84 B 3 Common Function Menus Cont 0 1 2 3 4 5 5 etc 6 7 8 9...
Страница 91: ...Appendix B Service Menus EY 65 H4 02 85 B 3 Common Function Menus Cont 0 1 2 3 4 5 10 11 or or 12 13...
Страница 92: ...Appendix B Service Menus EY 65 H4 02 86...
Страница 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Страница 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Страница 106: ...Index EY 65 H4 02 100...