Service Settings
EY.65.H4.02
68
10.4.5 Override
The setting pictures under the Override menu item include parameters that determine
the priority of the service water heating, the operation of heat circuits during night
setback, safety thermostat settings for individual circuits and mixing difference.
Hot-water priority
These settings determine how the controller should react if it is not possible to main-
tain the hot-water temperature at the setpoint specified by the user.
Display text
Parameter
Default value,
range
Description
Priority
Default value:
OFF
Range:
ON, OFF
When this parameter is set to ON, the
heating of water takes priority over the
heating of rooms
Max. devia-
tion
Maximum
deviation
Default value:
–5 K
Range:
–60-0 K
The number of degrees the hot-water
temperature or charging temperature is
allowed to drop below the setpoint be-
fore the priority function is activated.
1
When this happens, the motor valves to
the heat circuits are gradually closed
Flow temp.
diff.
Flow tem-
perature dif-
ference
Default value:
–20 K
Range:
–60-0 K
This parameter is active when Priority is
set to OFF, which means that the heat
circuit(s) and the hot-water circuit are
operated at the same time. An example is
illustrated in Figure 9 on page 69
In such a situation, the charging tem-
perature needed in the hot-water circuit
can be significantly above the calculated
flow temperature in the heat circuit. The
parameter Flow temp. diff. is used to
prevent the actual flow temperature in
the heat circuit from getting too high:
When Flow temp. diff. is exceeded, the
pump in the heat circuit is stopped
1
Whether it is the charging temperature or the hot-water temperature depends on the type of hot-water circuit.
More information about the hot-water priority of the various hot-water circuits is available in the ECL 2000
Technical Manual (ref. [3])
Содержание ECL 2000
Страница 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Страница 2: ......
Страница 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Страница 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Страница 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Страница 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Страница 88: ...Appendix B Service Menus EY 65 H4 02 82 B 2 Hot Water Service Menus 0 1 2 3 4 5 1 or or 2 or 3 4 or or...
Страница 89: ...Appendix B Service Menus EY 65 H4 02 83 B 3 Common Function Menus 0 1 2 3 4 5 1 2 etc 3 etc 4 etc...
Страница 90: ...Appendix B Service Menus EY 65 H4 02 84 B 3 Common Function Menus Cont 0 1 2 3 4 5 5 etc 6 7 8 9...
Страница 91: ...Appendix B Service Menus EY 65 H4 02 85 B 3 Common Function Menus Cont 0 1 2 3 4 5 10 11 or or 12 13...
Страница 92: ...Appendix B Service Menus EY 65 H4 02 86...
Страница 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Страница 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Страница 106: ...Index EY 65 H4 02 100...