![Danfoss D9h Скачать руководство пользователя страница 42](http://html2.mh-extra.com/html/danfoss/d9h/d9h_operating-manual_5121583042.webp)
•
•
•
-
4.7 Cooling Requirements
N O T I C E
OVERHEATING
Improper mounting can result in overheating and reduced performance.
Install the drive following the installation and cooling requirements.
Ensure that top and bottom clearance for air cooling is provided. Clearance requirement: 225 mm (9 in).
Provide sufficient airflow flow rate. See
.
Consider derating for temperatures starting between 45 °C (113 °F) and 50 °C (122 °F) and elevation 1000 m (3300 ft) above sea
level.
The enclosed drive, excluding the input power options cabinet, utilizes a back-channel cooling concept that removes the air used to
cool the heat sink. The heat sink cooling air carries approximately 90% of the heat out of the back channel of the drive. Different
back-channel cooling kits are available to redirect the airflow based on individual needs.
4.8 Airflow Rates
Table 39: Airflow Rates for D9h Enclosure
Cabinet
Back-channel fan [m
3
/hr (cfm)]
Drive module top fan [m
3
/hr (cfm)]
Cabinet door fan [m
3
/hr (cfm)]
PHF/line reactor
450 (265)
–
–
Drive
420 (250)
102 (60)
150 (90)
dU/dt
–
–
–
Sine-wave
900 (530)
–
–
Top entry/top exit
–
–
–
Table 40: Airflow Rates for D10h Enclosure
Cabinet
Back-channel fan [m
3
/hr (cfm)]
Drive module top fan [m
3
/hr (cfm)]
Cabinet door fan [m
3
/hr (cfm)]
PHF/line reactor
515 (303)
–
–
Input options
–
–
510 (310)
Drive
840 (500)
204 (120)
315 (185)
dU/dt
–
–
–
Sine-wave
900 (530)
–
–
Top entry/top exit
–
–
–
Table 41: Airflow Rates for E5h Enclosure
Cabinet
Back-channel fan [m
3
/hr (cfm)]
Drive module top fan [m
3
/hr (cfm)]
Cabinet door fan [m
3
/hr (cfm)]
PHF/line reactor
765 (450)
–
–
Input options
–
–
510 (310)
Drive
994 (585)
595 (350)
335 (200)
AQ262139143212en-000301 / 130R0879
42 | Danfoss A/S © 2021.10
Mechanical Installation
VLT® AutomationDrive FC 302
Operating Guide
Содержание D9h
Страница 2: ......
Страница 11: ...AQ262139143212en 000301 130R0879 11 Danfoss A S 2021 10 Introduction VLT AutomationDrive FC 302 Operating Guide...
Страница 12: ...AQ262139143212en 000301 130R0879 12 Danfoss A S 2021 10 Introduction VLT AutomationDrive FC 302 Operating Guide...
Страница 13: ...AQ262139143212en 000301 130R0879 13 Danfoss A S 2021 10 Introduction VLT AutomationDrive FC 302 Operating Guide...