FC 302
N200
N250
N315
Intermittent (60 s overload) (at 575/690 V) [A]
363
319
435
378
516
440
Continuous kVA (at 550 V) [kVA]
230
276
276
327
327
380
Continuous kVA (at 575 V) [kVA]
241
289
289
343
343
398
Continuous kVA (at 690 V) [kVA]
289
347
347
411
411
478
Maximum input current
Continuous (at 525 V) [A]
244
292
292
347
347
403
Continuous (at 575/690 V) [A]
233
279
279
332
332
385
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
2x185 (2x350 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm)
- Mains with disconnect [mm
2
(AWG)]
2x185 (2x350 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm)
- Mains with fusible disconnect [mm
2
(AWG)]
2x185 (2x350 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm)
- Mains with contactor [mm
2
(AWG)]
2x185 (2x350 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm)
- Motor [mm
2
(AWG)]
2x185 (2x350 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm)
Drive module power loss at 600 V [W]
(1)(2)(3)
3012
3723
3642
4465
4146
5028
Drive module power loss at 690 V [W]
(1)(2)(3)
3123
3851
3771
4614
4258
5155
Drive efficiency
(2)
0.98
0.98
0.98
Output frequency [Hz]
(4)
0–590
0–590
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [°C (°F)]
80 (176)
80 (176)
80 (176)
PHF overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
Line reactor overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
dU/dt filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
Sine-wave filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimension-
ing of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power
consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-direc-
tive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each
add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficien-
cy class, see the
Ambient Conditions
section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
3
See also
Input Power Option Losses
section.
4
If using an output filter, the output frequency is limited further. See
Table 107: Electrical Data, Mains Supply 3x525–690 V AC
FC 302
N355
N400
N500
High/normal overload
HO
NO
HO
NO
HO
NO
AQ262139143212en-000301 / 130R0879
168 | Danfoss A/S © 2021.10
Specifications
VLT® AutomationDrive FC 302
Operating Guide