FC 302
N355
N400
N500
Line reactor overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
dU/dt filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
Sine-wave filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimension-
ing of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power
consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-direc-
tive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each
add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficien-
cy class, see the
Ambient Conditions
section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
3
See also
Input Power Option Losses
section.
4
If using an output filter, the output frequency is limited further. See
Table 108: Electrical Data, Mains Supply 3x525–690 V AC
FC 302
N560
N630
N710
High/normal overload
High overload=150% or 160% torque for a duration of 60 s.
Normal overload=110% torque for a duration of 60 s.
HO
NO
HO
NO
HO
NO
Typical shaft output at 550 V [kW]
450
500
500
560
560
670
Typical shaft output at 575 V [hp]
600
650
650
750
750
950
Typical shaft output at 690 V [kW]
560
630
630
710
710
800
Enclosure size
E5h
E6h
E6h
Output current (3-phase)
Continuous (at 550 V) [A]
596
630
659
763
763
889
Intermittent (60 s overload) (at 550 V) [A]
894
693
989
839
1145
978
Continuous (at 575/690 V) [A]
570
630
630
730
730
850
Intermittent (60 s overload) (at 575/690 V) [A]
855
693
945
803
1095
935
Continuous kVA (at 550 V) [kVA]
568
600
628
727
727
847
Continuous kVA (at 575 V) [kVA]
568
627
627
727
727
847
Continuous kVA (at 690 V) [kVA]
681
753
753
872
872
1016
Maximum input current
Continuous (at 550 V) [A]
574
607
635
735
735
857
Continuous (at 575/690 V) [A]
549
607
607
704
704
819
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
4x127 (4x250 mcm) 4x185 (4x350 mcm) 4x185 (4x350 mcm)
- Mains with disconnect [mm
2
(AWG)]
4x127 (4x250 mcm) 4x185 (4x350 mcm) 4x185 (4x350 mcm)
- Mains with fusible disconnect [mm
2
(AWG)]
4x127 (4x250 mcm) 4x185 (4x350 mcm) 4x185 (4x350 mcm)
AQ262139143212en-000301 / 130R0879
170 | Danfoss A/S © 2021.10
Specifications
VLT® AutomationDrive FC 302
Operating Guide