AKD 5000
Programming
■
Parameters — Serial communication
500 Address
(BUS ADDRESS)
Value:
1 - 126
✭
1
Function:
This parameter allows specification of the address
of each frequency converter. This feature is used
in connection with PLC/PC connection.
Description of choice:
The individual frequency converters can be given an
address between 1 and 126. The address 0 is used
if a master (PLC or PC) wishes to send a telegram
that is to be received by all frequency converters
connected to the serial communication port at the
same time. In this case, the frequency converter
will not acknowledge receipt. If the number of units
connected (frequency conv master) exceeds
31, a repeater is required. Parameter 500 cannot be
selected via the serial communication port.
507 Selection of Setup
(SETUP SELECT)
Value:
Digital input (DIGITAL INPUT)
[0]
Bus (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
✭
Logic or (LOGIC OR)
[3]
Function:
Parameter 507 allows a choice between controlling
the frequency converter via the terminals (digital
input) and/or via the bus.
If
Logic and or Bus
is selected, the command
in question can only be activated if transmitted
via the serial communication port. In the case
of
Logic and
, the command must additionally be
activated via one of the digital inputs.
Description of choice:
Digital input
[0] is selected if the control command in
question is only to be activated via a digital input.
Bus
[1] is selected if the control command in
question is only to be activated via a bit in the
control word (serial communication).
Logic and
[2] is selected if the control command
in question is only to be activated when a signal
is transmitted (active signal = 1) via both a
control word and a digital input.
Logic or
[3] is selected if the control command in
question is to be activated when a signal is given (active
signal = 1) either via a control word or via a digital input.
513 Bus time interval
(BUS TIMEOUT TIME)
Value:
1 - 99 sec.
✭
1 sec.
Function:
This parameter sets the maximum time expected
to pass between the receipt of two consecutive
telegrams. If this time is exceeded, the serial
communication is assumed to have stopped and the
desired reaction is set in parameter 514.
Description of choice:
Set the desired time.
514 Bus time interval function
(BUS TIMEOUT FUNC)
Value:
Off (OFF)
[0]
Freeze output (FREEZE OUTPUT)
[1]
Stop (STOP)
[2]
Jogging (JOGGING)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
This parameter selects the desired reaction of the
frequency converter when the set time for bus timeout
(parameter 513) has been exceeded.
If choices [1] to [5] are activated, relay 01 and
relay 04 will be de-activated.
If more time-outs occur at the same time the
frequency converter will give the following priority
to the time-out function:
1. Parameter 318
Function after time out
2. Parameter 346
Function after encoder loss
3. Parameter 514
Bus time interval function.
Description of choice:
The output frequency of the frequency converter
can: be frozen at the present value, be frozen at
the reference, go to stop, go to jogging frequency
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.R3.02 -
93