AKD 5000
Programming
Select
Download all parameters
[2] if all transmitted
parameter values are to be copied to the frequency
converter on which the control panel has been mounted.
Select
Download power-independent par.
[3] if only the
power-independent parameters are to be downloaded.
This is used if downloading to a frequency converter
that has a different rated power that the one from
where the parameter Setup originates.
Please note that the power-dependent parameter
102-106 must be programmed after copying.
NB!:
Uploading/Downloading can only be carried
out in the Stop mode.
008 Display scaling of motor frequency
(FREQUENCY SCALE)
Value:
0.01 - 500.00
✭
1
Function:
This parameter chooses the factor to be multiplied
by the motor frequency, f
M
, for presentation in
the display, when parameters 009-012 have been
set for Frequency x Scaling [5].
Description of choice:
Set the desired scaling factor.
009 Display line 2 (DISPLAY LINE 2)
Value:
Reference [%] (REFERENCE [%])
[1]
Reference [unit] (REFERENCE [UNIT])
[2]
Feedback [unit] (FEEDBACK [UNIT])
[3]
✭
Frequency [Hz] (FREQUENCY [HZ])
[4]
Frequency x Scaling [-]
(FREQUENCY X SCALE)
[5]
Motor current [A] (MOTOR CURRENT [A])
[6]
Torque [%] (TORQUE [%])
[7]
Power [kW] (POWER [KW])
[8]
Power [HP] (POWER [HP] [US])
[9]
Output energy [kWh]
(OUTPUT ENERGY [KWH])
[10]
Motor voltage [V] (MOTOR VOLTAGE [V])
[11]
DC link voltage [V] (DC LINK VOLTAGE [V])
[12]
Thermal load, motor [%]
(MOTOR THERMAL [%])
[13]
Thermal load, AKD [%] (FC THERMAL [%])
[14]
Hours run [Hours] (RUNNING HOURS)
[15]
Digital input [Binary code]
(DIGITAL INPUT [BIN])
[16]
Analogue input 53 [V] (ANALOG INPUT 53 [V])
[17]
Analogue input 54 [V] (ANALOG INPUT 54 [V])
[18]
Analogue input 60 [mA]
(ANALOG INPUT 60 [MA])
[19]
Pulse reference [Hz] (PULSE REF. [HZ])
[20]
External reference [%] (EXTERNAL REF [%])
[21]
Status word [Hex] (STATUS WORD [HEX])
[22]
Brake effect/2 min. [KW]
(BRAKE ENERGY/2 MIN)
[23]
Brake effect/sec. [kW] (BRAKE ENERGY/S)
[24]
Heat sink temp. [°C] (HEATSINK TEMP [°C] )
[25]
Alarm word [Hex] (ALARM WORD [HEX])
[26]
Control word [Hex]
(CONTROL WORD [HEX])
[27]
Warning word 1 [Hex]
(WARNING WORD 1 [HEX])
[28]
Warning word 2 [Hex]
(WARNING WORD 2 [HEX])
[29]
Communication option card warning
(COMM OPT WARN [HEX])
[30]
RPM [min
-1
] (MOTOR RPM [RPM])
[31]
RPM x scaling [
-
] (MOTOR RPM X SCALE)
[32]
Function:
This parameter allows a choice of the data value
to be displayed in line 2 of the display.
Parameters 010-012 enable the use of three additional
data values to be displayed in line 1.
Description of choice:
Reference [%]
corresponds to the total reference
(sum of digital/analogue/preset/bus/freeze
ref./catch-up and slow-down).
Reference [unit]
gives the status value of terminals
17/29/53/54/60 using the unit stated on the basis of
configuration in parameter 100 (Hz, Hz and rpm).
Feedback [unit]
gives the status value of
terminal 33/53/60 using the unit/scale selected
in parameter 414, 415 and 416.
Frequency [Hz]
gives the motor frequency, i.e. the
output frequency from the frequency converter.
Frequency x Scaling [-]
corresponds to the present
motor frequency f
M
(without resonance dampening)
multiplied by a factor (scaling) set in parameter 008.
Motor current [A]
states the phase current of the
motor measured as effective value.
Torque [%]
gives the current motor load in
relation to the rated motor torque.
Power [kW]
states the actual power consumed
by the motor in kW.
Power [HP]
states the actual power consumed
by the motor in HP.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.R3.02 -
61