AKD 5000
Programming
If a setting in parameters 101-106 is changed,
parameter 221 is not automatically reversed
to the factory setting.
223 Warning: Low current
(WARN. CURRENT LO)
Value:
0.0 - parameter 224
✭
0.0 A
Function:
When the motor current is below the limit,
I
LOW
, programmed in this parameter, the display
indicates CURRENT LOW.
The signal outputs can be programmed to transmit a
status signal via terminal 42 or 45 as well as via relay
output 01 or 04 (parameter 319, 321, 323 or 326).
Description of choice:
The lower signal limit I
LOW
of the motor current
must be programmed within the normal working
range of the frequency converter.
224 Warning: High current
(WARN. CURRENT HI)
Value:
Parameter 223 - I
AKD,MAX
✭
I
AKD,MAX
Function:
f the motor current gets above the limit programmed
in this parameter, I
HIGH
, the display will indicate
CURRENT HIGH.
The signal outputs can be programmed to transmit a
status signal via terminal 42 or 45 and via relay output
01 or 04 (parameter 319, 321, 323 or 326).
Description of choice:
The upper signal limit of the motor current, I
HIGH
, must
be programmed within the normal working range of the
frequency converter. See drawing at parameter 223.
225 Warning: Low frequency
(WARN. FREQ. LOW)
Value:
0.0 - parameter 226
✭
0.0 Hz
Function:
When the motor frequency is below the limit
programmed in this parameter, f
LOW
, the display
indicates FREQUENCY LOW.
The signal outputs can be programmed to transmit a
status signal via terminal 42 or 45 and via relay output
01 or 04 (parameter 319, 321, 323 or 326).
Description of choice:
The lower signal limit of the motor frequency, f
LOW
,
is to be programmed within the normal working
range of the frequency converter.
226 Warning: High frequency
(WARN. FREQ. HIGH)
Value:
parameter 225 - parameter 202
✭
132.0 Hz
Function:
When the motor frequency is above the limit
programmed in this parameter, f
HIGH
, the display
will indicate FREQUENCY HIGH.
The signal outputs can be programmed to transmit a
status signal via terminal 42 or 45 and via relay output
01 or 04 (parameter 319, 321, 323 or 326).
Description of choice:
The upper signal limit of the motor frequency, f
HIGH
,
must be programmed within the normal working
range of the frequency converter.
227 Warning: Low feedback
(WARN. FEEDB. LOW)
Value:
-100,000.000 - parameter 228.
✭
-4000.000
Function:
If the connected feedback signal gets below the
value set in this parameter, the signal outputs can
be programmed to transmit a status signal via
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.R3.02 -
75
Содержание AKD 5001
Страница 12: ...AKD 5000 Introduction Ordering form AKD 5000 Series Typecode MG 50 R3 02 11 ...
Страница 25: ...AKD 5000 Type F IP54 MG 50 R3 02 24 ...
Страница 29: ...AKD 5000 Compact IP 54 AKD 5001 5006 200 240 V AKD 5001 5011 380 500 V MG 50 R3 02 28 ...