AKD 5000
■
Compact, Mains supply 3 x 380 - 500 V
According to international requirements
A
A
A
AK
K
K
KD
D
D
D tttty
yy
yp
p
p
pe
e
e
e
5
5
5
50
0
0
01
1
1
16
6
6
6
5
5
5
50
0
0
02
2
2
22
2
2
2
5
5
5
50
0
0
02
2
2
27
7
7
7
N
N
N
No
o
o
orrrrm
m
m
ma
a
a
allll o
o
o
ov
vv
ve
e
e
errrrllllo
o
o
oa
a
a
ad
d
d
d tttto
o
o
orrrrq
q
q
qu
u
u
ue
e
e
e ((((1
1
1
11
1
1
10
0
0
0 %
%
%
%))))::::
Output current
I
N
[A] (380-440 V)
32
37.5
44
I
MAX
(60 s) [A] (380-440 V)
35.2
41.3
48.4
I
N
[A] (441-500 V)
27.9
34
41.4
I
MAX
(60 s) [A] (441-500 V)
30.7
37.4
45.5
Output
S
N
[kVA] (380-440 V)
24.4
28.6
33.5
S
N
[kVA] (441-500 V)
24.2
29.4
35.8
Typical shaft output
P
N
[kW]
15
18.5
22
Typical shaft output
P
N
[HP]
20
25
30
H
H
H
Hiiiig
g
g
gh
h
h
h o
o
o
ov
vv
ve
e
e
errrrllllo
o
o
oa
a
a
ad
d
d
d tttto
o
o
orrrrq
q
q
qu
u
u
ue
e
e
e ((((1
1
1
16
6
6
60
0
0
0 %
%
%
%))))::::
Output current
I
N
[A] (380-440 V)
24
32
37.5
I
MAX
(60 s) [A] (380-440 V)
38.4
51.2
60
I
N
[A] (441-500 V)
21.7
27.9
34
I
MAX
(60 s) [A] (441-500 V)
34.7
44.6
54.4
Output
S
N
[kVA] (380-440 V)
18.3
24.4
28.6
S
N
[kVA] (441-500 V)
18.8
24.2
29.4
Typical shaft output
P
N
[kW]
11
15
18.5
Typical shaft output
P
N
[HP]
15
20
25
Max. cable cross-section to motor,
IP 54
16/6
16/6
16/6
brake and loadsharing [mm
2
]/[AWG]
2) 4)
IP 20
16/6
16/6
35/2
Min. cable cross-section to motor,
brake and loadsharing [mm2]/[AWG]
10/8
10/8
10/8
Rated input current
I
L,N
[A] (380 V)
32
37.5
44
I
L,N
[A] (460 V)
27.6
34
41
Max. cable cross-section,
IP 54
16/6
16/6
16/6
power [mm
2
]/[AWG]
IP 20
16/6
16/6
35/2
Max. pre-fuses
[-]/UL
1)
[A]
63/40
63/50
63/60
Pre-fuse SMPS
[-]/UL
5)
[A]
4.0/4.0
4.0/4.0
4.0/4.0
Efficiency
0.96
0.96
0.96
Weight IP 20 EB
[kg]
21
22
27
Weight IP 54
[kg]
41
41
42
Power loss at max. load.
- high overload torque
(160 %)
[W]
419
559
655
- normal overload
torque (110 %)
[W]
559
655
768
Enclosure
IP
20/IP54
IP
20/IP54
IP
20/IP54
1. For type of fuse see section
Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20.
Always comply with national and local regulations on min. cable cross-section.
5. If UL/cUL is to be complied with, Ferraz shawmut type FA Y85443, Danfoss ordering no. 612Z1182 must be used.
MG.50.R3.02 -
20
Содержание AKD 5001
Страница 12: ...AKD 5000 Introduction Ordering form AKD 5000 Series Typecode MG 50 R3 02 11 ...
Страница 25: ...AKD 5000 Type F IP54 MG 50 R3 02 24 ...
Страница 29: ...AKD 5000 Compact IP 54 AKD 5001 5006 200 240 V AKD 5001 5011 380 500 V MG 50 R3 02 28 ...
Страница 33: ...AKD 5000 MG 50 R3 02 32 ...