AKD 5000
■
Display - Status messages
Status messages appear in the 4th line of the display,
see the below example. The status message will
be on the display for approx. 3 seconds.
20.0Hz
SLOW DOWN
FREQUENCY
Start clockwise/anti-clockwise
(START FORW./REV):
Input on digital inputs and parameter data are in conflict.
Slow-down (SLOW DOWN):
The output frequency of the frequency converter
is reduced by the percentage value chosen
in parameter 219.
Catch-up (CATCH UP):
The output frequency of the frequency converter
is increased by the percentage value chosen
in parameter 219.
Feedback high (FEEDBACK HIGH):
The FB value is higher than the value set in
parameter 228. This message is only shown
when the motor is running.
Feedback low (FEEDBACK LOW):
The FB value is lower than the value set in
parameter 227. This message is only shown
when the motor is running.
Output frequency high (FREQUENCY HIGH):
The output frequency is higher than the value set
in parameter 226. This message is only shown
when the motor is running.
Output frequency low (FREQUENCY LOW):
The output frequency is lower than the value set
in parameter 225. This message is only shown
when the motor is running.
Output current high (CURRENT HIGH):
The output current is higher than the value set
in parameter 224. This message is only shown
when the motor is running.
Output current low (CURRENT LOW):
The output current is lower than the value set
in parameter 223. This message is only shown
when the motor is running.
Ramp operation (REM/ RAMPING):
Remote
has been selected in parameter 002 and
the output frequency is changed in accordance
with the ramps set.
Ramp operation (LOCAL/ RAMPING):
Local
has been selected in parameter 002 and
the output frequency is changed in accordance
with the ramps set.
Running, local control (LOCAL/RUN OK):
Local control has been selected in parameter 002
and a start command is given on either terminal 18
(START or LATCHED START in parameter 302) or
terminal 19 (START REVERSE parameter 303).
Running, remote control (REM/RUN OK):
Remote control has been selected in parameter 002 and
a start command is given on either terminal 18 (START
or LATCHED START in parameter 302), terminal 19
(START REVERSE parameter 303) or via the serial bus.
AKD ready, remote control (REM/UNIT READY):
Remote control
has been selected in parameter
002 and
Coasting stop
inverse in parameter 304,
and there is 0 V on terminal 27.
AKD ready, local control (LOCAL/ UNIT READY):
Local
has been selected in parameter 002
and
Coasting inverse
in parameter 304, and
there is 0 V on terminal 27.
Quick-stop, remote control (REM/QSTOP):
Remote control
has been selected in parameter
002 and the frequency converter has stopped via
a quick-stop signal on terminal 27 (or possibly
via the serial communication port).
Quick-stop, local (LOCAL/ QSTOP):
Local
has been selected in parameter 002 and
the frequency converter has stopped via a
quick-stop signal on terminal 27 (or possibly via
the serial communication port).
DC stop, remote control (REM/DC STOP):
Remote control
has been selected in parameter
002 and the frequency converter has stopped via
a DC stop signal on a digital input (or possibly
via the serial communication port).
Stop, remote controlled (REM/STOP):
MG.50.R3.02 -
102